1-805-484-2992

Quotes - Sizing - Sales

Greenhouse & Vertical Farm Cooling

Fan-Coil & Grow-Room Temperature Control

Overview

Grow lights and solar gain both add heat a greenhouse or vertical farm has to remove on a schedule the crop sets, not the weather.

A greenhouse's cooling load comes from two directions at once - solar gain through the glazing and heat thrown off by supplemental lighting - and a fan-coil loop fed by a glycol chiller is what pulls that heat back out to hold the crop's target range. Because solar gain swings hard between a clear day and an overcast one, the loop has to be sized against peak simultaneous gain, not a seasonal average.

A sealed indoor vertical farm faces a related but distinct problem: nearly all of its heat load comes from grow lighting and equipment rather than the sun, and because the space is sealed rather than naturally ventilated, that heat has nowhere to go without mechanical cooling. Grow-room cooling loads scale directly with lighting wattage per square foot, which makes them more predictable to size than a greenhouse's weather-driven load, but no less real.

Both applications typically run a chilled or glycol water loop rather than direct refrigerant to the grow space, which keeps the cooling equipment itself out of the growing environment and simplifies service access.

  • Greenhouse loads are sized against peak simultaneous solar gain, not a seasonal average
  • Vertical farm grow-room load scales with lighting wattage per square foot
  • A glycol water loop keeps cooling equipment out of the growing environment itself
Vertical farm grow racks under LED lighting beside a packaged cooling unit
In a sealed vertical farm the heat comes from the grow lights, so the load scales with lighting wattage and typically runs on 45-55°F leaving fluid.
Greenhouse fan-coil
40-50°F
Vertical farm grow room
45-55°F
Greenhouse glycol mix
20-25% propylene
Vertical farm load
Steady, lighting-cycle

Sizing Greenhouse & Vertical Farm Cooling

Greenhouse tonnage is driven by glazing area and peak solar gain for your latitude, plus any supplemental lighting load - it is not a simple square-footage rule of thumb. Vertical farm tonnage is more predictable: it scales almost directly with installed grow-light wattage per square foot, since the sealed room has no other significant heat path in or out.

Both applications commonly run a single packaged glycol chiller feeding a fan-coil (greenhouse) or grow-room air handler (vertical farm) loop, with the reservoir/pump skid sized for the loop's total flow rather than any single coil.

Send Us

  • Glazing area or grow-room square footage
  • Installed lighting wattage
  • Target leaving fluid / room temperature
  • Indoor or outdoor chiller placement

TYPICAL RANGES BY OPERATION

OperationLeaving Fluid TempLoad ProfileTypical Glycol Mix
Greenhouse fan-coil40-50°FWeather-driven, day peak20-25% propylene
Vertical farm grow room45-55°FSteady, lighting-cycle driven15-20% propylene
Combined grow + equipment room35-45°FMixed, continuous baseline20-30% propylene

Ranges are typical starting points, not a substitute for a load calculation - actual leaving fluid temperature and glycol percentage depend on your glazing, lighting and local climate.
Call and talk it through with an engineer: 1-805-484-2992.

Before You Size Greenhouse or Grow-Room Cooling

The whole loop drops to the colder setpoint and the stronger mix, because one chiller makes one leaving temperature. Per the typical ranges, a grow room alone runs 45-55°F on 15-20% propylene, while a combined grow and equipment room loop runs 35-45°F on 20-30%. That 10°F drop cuts what the same chiller delivers, so a unit selected at a grow-room rating comes up short once the equipment room is tied in. The chiller has to be selected at the colder leaving temperature; what a mixing valve on the grow-room branch adds is coils that do not overcool the crop. Either way, the fill follows the colder circuit.

Because the lights do not follow the season: a sealed grow room's heat comes from its lighting schedule, so January load looks much like July's. A greenhouse is different, since its solar peak falls away in winter. For a vertical farm the chiller runs hard in cold weather, and an outdoor unit has to be specified for that, with a glycol mix set for the coldest night on the pad and a package able to keep rejecting heat in low outdoor temperatures. Send your winter design temperature with the lighting load so the outdoor package is selected for both.

From the total flow every coil draws at the same moment on a clear afternoon, plus the pressure drop to the farthest coil. On a water basis, GPM equals the BTU/hr load over 500, then over the rise in degrees. Take a 20-ton greenhouse load: that is 240,000 BTU/hr, so a 10°F rise needs 48 GPM and a 6°F rise needs 80 GPM. On glycol the real figure runs slightly higher. The common mistake is assuming coils cycle and sizing for a fraction of them; on a peak-sun day every valve is open together. Tell us the coil count, the design rise and the longest pipe run.

Yes, a colder coil condenses more moisture, but every degree lower costs chiller capacity. Growers who need more dehumidification sometimes run toward the bottom of the 45-55°F grow-room range, or down in to the 35-45°F combined-loop range, which takes 20-30% propylene instead of 15-20%. Check the chiller's capacity at the lower leaving temperature and the mix before moving down, or a unit that held the room in spring falls behind in summer.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales