Tonnage & Capacity Guide

How Capacity Scales From Portable to Central

Overview

A ton of refrigeration is a fixed unit of heat removal - what changes as you move up in tonnage is the equipment format that delivers it.

One ton of refrigeration equals 12,000 BTU/hr of heat removal - a fixed unit regardless of chiller size or manufacturer. What changes as tonnage climbs is the equipment format: small loads are typically served by self-contained portable units, mid-size and larger loads move to packaged central or outdoor systems, and the largest or most site-specific jobs use modular or add-on configurations built up from multiple compressor circuits.

There's real overlap between formats rather than a hard cutoff - a load in the middle range can often be served by either a larger portable unit or a smaller central package, and the right choice usually comes down to footprint, redundancy needs, and whether the load is likely to grow. A single fermenter's jacket cooling might sit comfortably on a portable chiller, while the same tonnage feeding a shared plant-wide glycol loop is a better fit for a central system with add-on capacity built in.

Because format and tonnage interact rather than mapping one-to-one, we size against your actual heat load and site conditions rather than a chart alone - see How to Size a Glycol Chiller for the underlying calculation, or send us your numbers directly for a rating that accounts for both.

  • 1 ton of refrigeration = 12,000 BTU/hr, a fixed unit independent of equipment format
  • Small loads: typically portable. Larger loads: typically central, packaged or modular
  • Format overlaps in the mid-range - footprint, redundancy and growth plans decide it, not tonnage alone
1

Add up the load

Total heat across everything the chiller will serve

2

Count process points

Several lines on one loop point toward central

3

Pick the format

Portable to roughly 40 tons, modular above roughly 210

4

Plan for growth

Redundancy and expansion shift where a load lands

Matching Format to Load

Tonnage tells you how much heat a chiller removes; format tells you what shape of equipment does it. The two interact rather than mapping one-to-one, which is why the table below is a starting reference, not a strict lookup - footprint, redundancy needs and growth plans all shift where a given load actually lands.

A single-line brewery or a small compressor loop typically sits comfortably on a portable unit; a multi-line plant or a facility running several process points off one loop typically makes more sense on a packaged central system, even at a tonnage a large portable unit could technically cover.

Send Us

  • Total heat load across everything the chiller will serve
  • Number of separate process points or lines feeding the loop
  • Available footprint and whether it's indoors or outdoors
  • Growth plans - is the load likely to increase in the next few years
  • Redundancy requirements, if any process point can't tolerate downtime

FORMAT BY TONNAGE RANGE

FormatTypical Tonnage RangeTypical Install
Portable / packagedUp to roughly 40 tonsIndoor or outdoor, single line or process point
Packaged central systemRoughly 40 to 180-210 tonsMulti-line plant or shared plant-wide loop
Modular / custom systemAbove roughly 210 tonsLarge or highly site-specific installations

Ranges overlap by design - the right format for a mid-range load depends on your site, not tonnage alone. The units in each range are listed on its own page: under 5 tons, 5 to 40, 40 to 100, 100 to 210 and 210+ tons.
Call and talk it through with an engineer: 1-805-484-2992.

Tonnage and Format: What to Know Before Sizing

Within one format, generally yes, but across formats size and tonnage stop tracking: a large portable and a central system of similar tonnage look nothing alike. Tonnage fixes only the heat removed, 12,000 BTU/hr for each ton. The cabinet depends on the format, on whether the unit is air- or water-cooled, and on whether a tank and pump are built in. A water-cooled unit, for instance, can be compact because its heat goes to condenser water instead of a large air coil. Send the space you have with the load, and the format is chosen to fit both.

They push a mid-range load toward more than one compressor circuit or more than one unit, even where a single unit could carry the tonnage. If a process point cannot tolerate downtime, a single portable on that load is a single point of failure; splitting the duty across circuits or units keeps part of the capacity running through a fault or a service call. That is one reason a load a large portable could cover may be better served by a central system or paired units. Tell us which process points cannot go down.

No; above roughly 210 tons the system is built from several compressor circuits or modules working together rather than one large machine. That changes the questions: how capacity stages as the load rises and falls, how much remains with one circuit or module down, and how the plant is laid out and piped. Redundancy comes with the architecture, which a single large unit cannot offer. Because the answers depend on the plant, these systems go to an application specialist rather than being picked from a table.

Add the loads that run at the same time, each at its peak, rather than every line's peak regardless of schedule. Convert each line's load to BTU/hr, sum the ones that coincide, and divide by 12,000 for tons. If two lines never run together, the chiller only needs to cover the larger of the pair, not their sum. Where schedules are uncertain or likely to change, total them all, because an undersized shared loop starves every line at once. The number of lines also matters: several process points on one loop lean toward a central system.