Dual-zone TTOACS packages to 188 tons, or condensers on the roof

Request a Quote

Air-Rejected Plants to 188 Tons

TTOACS, TTI Air-Cooled and MA Modules, 103 to 188 Tons

A large plant with no cooling tower rejects its heat to the air. At this size the two ways of doing it look very different on site: a TTOACS dual-zone package is a single frame with a 400- to 900-gallon tank on a yard pad, while a TTI air-cooled chiller or MA module sits in a mechanical room and pipes refrigerant to condensers outdoors.

The TTOACS packages here are rated 110.1 to 188 tons, all dual-zone. The TTI air-cooled central chillers run 120 to 180 tons and the MA modules 103 to 180 tons, on two or three zones or circuits.

Air-cooled chilling module for a remote condenser, representative unit

WHAT TO SPECIFY

  • Outdoor package: 288 to 490 GPM of pump and 400 to 900 gallons of tank on one frame.
  • Designed to run in ambient air from -20°F to 95°F.
  • Remote condensers: the TTI air-cooled units and MA modules connect to outdoor condensers through refrigerant lines installed in the field.
  • The chiller, its controls and its tank stay in a heated room.
  • Ratings: select from the rated figure - the TTOACS-190D and TTOACS-210D are rated 170.1 and 188 tons.
  • Electrical: the TTI and MA units are published at 230V, 460V and 575V; for the larger TTOACS packages we confirm it with the quote.
188 tons

Top single-unit rating on this pageThe TTOACS-210D carries 210 in its name and 188 in its rating at 50°F. Select from the rated figure, and plan two or more units on a common header for anything larger.

At 28°F glycol

What the Largest Units Deliver

1.

TTOACS-210D


Rated 188 tons at 50°F.

About 105 tons at 28°F.

2.

TTI-180A


Rated 180 tons at 50°F.

About 100 tons at 28°F.

3.

MA-180-RC-CCC


Rated 180 tons at 50°F.

About 100 tons at 28°F.

OUTDOOR AND REMOTE-CONDENSER SYSTEMS, 100 TO 210 TONS

Part Number Series Tons (50°F) Condenser Tank / Pump
TTI-120A TTI Air-Cooled 120 Remote Air-Cooled 360 GPM
TTI-120AD TTI Air-Cooled 120 Remote Air-Cooled 1,200 gal / 360 GPM
TTI-150A TTI Air-Cooled 135 Remote Air-Cooled 1,200 gal / 450 GPM
TTI-180A TTI Air-Cooled 180 Remote Air-Cooled 1,200 gal / 540 GPM
MA-105-RC-CCC MA Modules 103 Remote Air-Cooled Separate
MA-120-RC-CC MA Modules 120 Remote Air-Cooled Separate
MA-120-RC-CCC MA Modules 120 Remote Air-Cooled Separate
MA-150-RC-CCC MA Modules 135 Remote Air-Cooled Separate
MA-180-RC-CCC MA Modules 180 Remote Air-Cooled Separate
TTOACS-120D-MZC-2P TTOACS 110.1 Air-Cooled 400 gal / 288 GPM
TTOACS-150D-MZC-2P TTOACS 145.8 Air-Cooled 900 gal / 350 GPM
TTOACS-190D-MZC-2P TTOACS 170.1 Air-Cooled 900 gal / 451 GPM
TTOACS-210D-MZC-2P TTOACS 188 Air-Cooled 900 gal / 490 GPM

Figures are rated at 50°F leaving water. TTI air-cooled and MA units appear without their remote condensers, and the MA modules rely on a separate reservoir and pumping system.

Yard Package or Remote Condenser

Dual-zone TTOACS packages to 188 tons on a pad, or TTI chillers and MA modules indoors with their condensers on the roof.

A TTOACS package concentrates the whole plant in one place that a crane can set and a technician can walk around. It needs yard space, a structural pad and a power feed, and nothing inside the building but the header. Service happens outdoors, which in a northern winter is a real consideration for a plant that cannot wait for spring.

Remote condensers at this size

A 180-ton TTI-180A or MA-180-RC-CCC keeps its compressors indoors and rejects heat through condensers on the roof or a pad. The refrigerant line set is the critical part of the installation: long runs and large lifts need a refrigeration contractor who designs them for oil return and charge, and the installation quote should say so.

Past 188 tons

No single unit here is rated above 188 tons. A plant that needs more at its setpoint is built from two or more units on a common header, as the 210+ ton pages show.

The other line we supply covers this range as well - see its air-cooled chilling modules for remote condensers on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Operating Questions: Air-Rejected Plants to 188 Tons

About 36 tons more rating, more than twice the tank and a larger pump: 145.8 tons, 900 gallons and 350 GPM against 110.1 tons, 400 gallons and 288 GPM. On a 28°F loop the two come to roughly 81 and 61 tons. The tank jump matters most for batch work, since the 150D carries about 6.2 gallons per ton of rating where the 120D carries about 3.6. One practical difference sits outside the cooling: the TTOACS-120D has a published 460V rating, while the 150D's electrical data is confirmed with the quote, so state the plant voltage early if the larger package is under consideration.

Roughly 52 tons, half of the 105 or so the package holds at 28°F, since each of its two zones carries about half the rating. That keeps a cold loop alive at reduced load, but it won't hold a production schedule planned around the whole unit. Decide in advance which loads get shed during a zone repair and write that list into the controls narrative, so the night shift isn't deciding it. If nothing can be shed, the plant needs a second package on the header, not a bigger single one.

When the plant has a heated mechanical room and wants its compressors, controls and tank kept out of the weather. On a cold loop the two hold about the same, roughly 100 tons at 28°F from the TTI-180A and 105 from the TTOACS-210D, so the choice turns on the site. The TTI brings a 1,200-gallon tank and a 540 GPM pump indoors and needs rooftop or pad-mounted condensers, joined by a field-built refrigerant line set. The TTOACS carries 900 gallons and 490 GPM on one yard frame and needs only the header and power run out to it. Voltage can settle it too: the TTI is published at 575V, while the larger TTOACS packages have their electrical data confirmed with the quote.

The 900-gallon tank plus every foot of header and yard piping plus the process side, so order the mix against the whole system volume, not the tank figure. Because the package sits outdoors and is designed to run down to -20°F ambient, the mix has to protect the coldest exposed run on the coldest night, which on a northern site can call for more glycol than the process setpoint alone would. Take the piping volume from the drawings before ordering. Plants that fill from the tank number tend to run short and end up topping off with a weaker mix.

When an existing tank and pump station on site can carry the added flow, since the MA module is the refrigeration alone and draws from that station. Ratings line up closely: the MA-120-RC-CC and MA-120-RC-CCC match the TTI-120A at 120 tons, and the MA-180-RC-CCC matches the TTI-180A at 180. What changes is what arrives on site. The TTI-180A brings its own 1,200-gallon tank and 540 GPM pump; the module brings neither. The MA line also offers a 103-ton step, the MA-105-RC-CCC, which the TTI air-cooled list does not. Both reject heat through remote condensers, so the outdoor work is the same either way.