MA and MW modules added a step at a time past 210 tons

Request a Quote

Capacity Added in Steps

MA and MW Chilling Modules, 60 to 180 Tons Each

A plant-wide glycol system is a distribution system first - a tank, supply pumps, a header and return piping - with refrigeration attached to it. Built that way, capacity can be added a module at a time as the plant grows, without replacing the pumps or the tank.

The MA and MW chilling modules are built for exactly that. Each is the refrigeration section of a central chiller on its own frame, with one, two or three circuits, and needs a separate reservoir and pumping system. The MA modules reject heat through a remote air-cooled condenser outdoors, the MW modules to tower or city water. This page lists the 22 modules from 60 to 180 tons.

Water-cooled chilling module, representative unit

WHAT TO SPECIFY

  • Distribution: size the tank, supply pumps and header for the plant's final load, not the first module.
  • Each module draws from and returns to the plant tank.
  • Heat rejection: MA modules to remote air-cooled condensers, MW modules to tower or city water.
  • The two can be mixed on one plant.
  • Circuits: C, CC and CCC for one, two and three; the same rating is often offered two ways, such as the MW-120-CC and MW-120-CCC.
  • Voltage: 230V, 460V or 575V three-phase.
600 tons

Five MW-120-CCC modules on one tankBuilt in steps from two modules to five, the example plant still carries 400 tons with any one module down. The tank, pumps and header are sized for the finished plant from day one.

At 50°F rating

Growing a Plant to 400 Tons

1.

Start


Tank, pumps and header sized for the final plant.

Two MW-120-CCC modules: 240 tons.

2.

Grow


Two more as the load arrives: 480 tons.

Each added while the others keep the loop running.

3.

Finish


A fifth module: 600 tons.

Carries 400 tons with any one module down.

CHILLING MODULES FROM 60 TO 180 TONS

Part Number Series Tons (50°F) Circuits Condenser Shipping Weight Voltage
MA-60-RC-C MA Modules 60 1 Remote Air-Cooled 1,400 lbs 230V / 460V / 575V
MA-60-RC-CC MA Modules 60 2 Remote Air-Cooled 2,350 lbs 230V / 460V / 575V
MA-70-RC-CC MA Modules 70 2 Remote Air-Cooled 2,500 lbs 230V / 460V / 575V
MA-80-RC-CC MA Modules 80 2 Remote Air-Cooled 2,600 lbs 230V / 460V / 575V
MA-100-RC-CC MA Modules 90 2 Remote Air-Cooled 3,450 lbs 230V / 460V / 575V
MA-90-RC-CCC MA Modules 90 3 Remote Air-Cooled 3,300 lbs 230V / 460V / 575V
MA-105-RC-CCC MA Modules 103 3 Remote Air-Cooled 3,450 lbs 230V / 460V / 575V
MA-120-RC-CC MA Modules 120 2 Remote Air-Cooled 3,700 lbs 230V / 460V / 575V
MA-120-RC-CCC MA Modules 120 3 Remote Air-Cooled 3,600 lbs 230V / 460V / 575V
MA-150-RC-CCC MA Modules 135 3 Remote Air-Cooled 3,900 lbs 230V / 460V / 575V
MA-180-RC-CCC MA Modules 180 3 Remote Air-Cooled 4,200 lbs 230V / 460V / 575V
MW-60-C MW Modules 60 1 Water-Cooled 1,400 lbs 230V / 460V / 575V
MW-60-CC MW Modules 60 2 Water-Cooled 2,350 lbs 230V / 460V / 575V
MW-70-CC MW Modules 70 2 Water-Cooled 2,500 lbs 230V / 460V / 575V
MW-80-CC MW Modules 80 2 Water-Cooled 2,600 lbs 230V / 460V / 575V
MW-90-CCC MW Modules 90 3 Water-Cooled 3,300 lbs 230V / 460V / 575V
MW-100-CC MW Modules 100 2 Water-Cooled 3,450 lbs 230V / 460V / 575V
MW-105-CCC MW Modules 103 3 Water-Cooled 3,450 lbs 230V / 460V / 575V
MW-120-CC MW Modules 120 2 Water-Cooled 3,700 lbs 230V / 460V / 575V
MW-120-CCC MW Modules 120 3 Water-Cooled 3,600 lbs 230V / 460V / 575V
MW-150-CCC MW Modules 135 3 Water-Cooled 3,900 lbs 230V / 460V / 575V
MW-180-CCC MW Modules 180 3 Water-Cooled 4,200 lbs 230V / 460V / 575V

Ratings at 50°F leaving water. Every module connects to a separate reservoir and pumping system; MA modules are listed without their remote condensers.

Design the Distribution First

MA and MW chilling modules added to a plant's own tank and pump station, a step at a time, as the load grows past 210 tons.

The mistake that limits a plant-wide system is a header or pump set sized for the first phase. Adding a module is quick; replacing a 4-inch header with an 8-inch one is a shutdown. Size the tank, pumps and main piping for the plant the site expects to become, and leave valved, capped connections for the modules still to come.

Air or water for each module

MA and MW modules can sit side by side on the same tank. A plant with tower capacity to spare adds MW modules; one without adds MA modules and places their condensers outdoors. Their ratings match closely - the MA-120-RC-CC and MW-120-CC are both 120 tons at 50°F and both ship at 3,700 lbs - so the choice is heat rejection, not capacity.

Ratings below the name

Three module names run ahead of their ratings: the MA-100-RC-CC is rated 90 tons, and the MA-150-RC-CCC and MW-150-CCC 135 tons at 50°F. The table lists the rated figures.

The other line we supply covers this range as well - see it's add-on chiller modules for plant-wide systems to 300 tons on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

MA and MW Add-On Modules in Practice

At 60 tons a second circuit adds 950 lbs, but at 120 tons the three-circuit modules ship 100 lbs lighter than the two-circuit ones. The MA-60-RC-C and MW-60-C ship at 1,400 lbs and the CC versions at 2,350, all rated 60 tons. At 120 tons the MA-120-RC-CCC and MW-120-CCC come in at 3,600 lbs against 3,700 for the CC models. For a plant on a mezzanine or a light slab, check the table at the size in question rather than assuming more circuits always means more weight. Where the weights are close, the extra circuit is usually worth having for its finer capacity step and the larger share it leaves running when one circuit is down.

Yes. Module sizes can share one tank and header, and a 60-ton unit running alone at night usually holds setpoint more steadily than a 120-ton module turned down to half. In the example plant here, built toward five MW-120-CCC modules, add an MW-60-CC alongside them and let the plant controller lead with it whenever the load drops below about 60 tons at 50°F. The two-circuit version gives two steps of roughly 30 tons, which suits a night load that wanders; the single-circuit MW-60-C, at 1,400 lbs, is lighter but stops entirely if its one circuit trips. During the day the small module simply joins the staging sequence as one more step.

Yes: four MW-180-CCC modules, 720 tons at 50°F, still carry 540 with one down, against five MW-120-CCC modules in the page's 600-ton example. The larger modules save one frame and its connections but ship heavier, 4,200 lbs each against 3,600, so the four total 16,800 lbs against 18,000 for five. The real trade is granularity. With 180-ton modules every step the plant adds is 180 tons, and the module held as the spare is a larger investment sitting idle. With 120-ton modules the plant grows in smaller steps that track the load more closely, and the redundant module costs less. A plant whose future load is uncertain usually prefers the smaller steps.

Enough to matter. Five MW-150-CCC modules sound like 750 tons but are rated 675, and with one down they hold 540 instead of the 600 the names imply. Smaller gaps sit in the MA-100-RC-CC, rated 90 tons, and in the MA-105-RC-CCC and MW-105-CCC, both rated 103. The error usually surfaces at the end of the build-out, when the last planned module goes in and the plant still can't hold its design load with one module down. Count every phase from the rated column, then apply the multiplier for your setpoint.

An MA module brings a remote air-cooled condenser to be set outdoors, while an MW module brings a condenser-water connection to a tower or city supply. The MA weights in the table leave the condensers out, so roof or pad loading for them is a separate line in the plan, and the refrigerant piping between module and condenser is field work. On the MW side the tower takes the hit: its flow and its water treatment have to cover the new module before it is tied in. The process side looks the same for both, since each kind takes supply from the shared plant tank and sends its return back there.