Single- and dual-zone TTOACS units on a pad outside

Request a Quote

The Plant Outside, the Load Inside

TTOACS Units, 5.3 to 38.4 Tons

An outdoor packaged chiller moves everything that makes noise and heat out of the building. The air-cooled condenser, the compressors, the reservoir and the pumps arrive as one package, set on a pad or a roof curb, and only the supply and return lines come through the wall. Inside, the process room loses no floor space and gains no heat.

The TTOACS units on this page run from 5.3 to 38.4 tons at 50°F. Eight are single-zone (the S models) and three are dual-zone, with two refrigeration zones (the D models, from 20.2 tons). All are published at 460V three-phase for 20°F to 70°F fluid, and are designed to run in ambient air from -20°F to 95°F.

Outdoor packaged glycol chiller, representative unit

WHAT TO SPECIFY

  • Site: a level pad or curb with clearance around the condenser for airflow and service.
  • Fluid: a 20°F to 70°F supply; where winter air drops below freezing, the loop carries glycol with a freeze point below the coldest outdoor temperature.
  • Tank and pump: 65 to 200 gallons and 12 to 96 GPM, sized at about 2.4 GPM per ton.
  • Zones: single-zone to 38.4 tons; dual-zone from 20.2 tons for a second capacity step and redundancy.
  • Power: 460V three-phase; 16.6 full-load amps on the TTOACS-5S up to 110.2 on the TTOACS-40D.
  • Setpoint multipliers: 0.80 at 40°F, 0.60 at 30°F, 0.40 at 20°F.
460V

The one voltage published in this rangeEvery TTOACS unit from 5.3 to 38.4 tons is three-phase at this voltage. A site with only 208V or 230V should say so before selection, since an indoor unit may be the simpler route.

Cold climates

Winter Is the Design Case

1.

Glycol


An outdoor loop runs glycol even at a 50°F setpoint.

The freeze point has to beat the coldest night, not the setpoint.

2.

Ambient


Designed to run from -20°F to 95°F.

Summer is when to check capacity.

3.

Piping


Supply and return lines outside the building are insulated.

Every exposed section carries protected fluid.

OUTDOOR PACKAGED UNITS, 5 TO 40 TONS

Part Number Series Tons (50°F) Zones Process Flow Reservoir Full Load Amps (460V)
TTOACS-5S-CG-1P TTOACS 5.3 1 12 GPM 68 gal 16.6
TTOACS-7.5S-CG-1P TTOACS 7.8 1 18 GPM 65 gal 22.8
TTOACS-10S-CG-1P TTOACS 10.2 1 24 GPM 68 gal 28.5
TTOACS-15S-CG-1P TTOACS 14.4 1 36 GPM 68 gal 45.0
TTOACS-20S-CG-1P TTOACS 18.9 1 48 GPM 68 gal 52.0
TTOACS-20D-MZC-2P TTOACS 20.2 2 48 GPM 150 gal 59.2
TTOACS-25S-CG-1P TTOACS 24.2 1 60 GPM 100 gal 67.9
TTOACS-30D-MZC-2P TTOACS 27.7 2 72 GPM 200 gal 92.8
TTOACS-30S-CG-1P TTOACS 28.8 1 72 GPM 100 gal 82.3
TTOACS-40D-MZC-2P TTOACS 37.2 2 96 GPM 200 gal 110.2
TTOACS-40S-CG-1P TTOACS 38.4 1 96 GPM 100 gal 102.3

Ratings at 50°F leaving water. Every model here is published at 460V three-phase.

Single-Zone or Dual-Zone?

Single- and dual-zone TTOACS units that put the whole refrigeration plant on a pad outside, rated to run from -20°F to 95°F ambient.

A single-zone unit is one refrigeration system on one tank. It is the right choice for a steady load with a planned maintenance window. A dual-zone unit carries two refrigeration zones: at part load one zone can carry the process, and a fault in one zone leaves the other running. For a brewery cellar or a food line that cannot stop for a compressor repair, the D models from 20.2 tons are the usual pick.

Select from the rating, not the name

Model names round to a size class; the ratings do not. The TTOACS-40S-CG-1P is rated 38.4 tons and the TTOACS-30D-MZC-2P 27.7 tons at 50°F. Select from the rating in the table, then apply the multiplier for your setpoint: 38.4 tons at 50°F is about 23 tons at 30°F.

Where the outdoor range continues

Single-zone outdoor units run to 55.1 tons and dual-zone units to 188 tons, on the 40 to 100 ton and 100 to 210 ton outdoor pages.

The other line we supply covers this range as well - see its outdoor glycol chillers on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Before You Order an Outdoor Packaged Chiller

From the published full-load amps of the exact model, which run from 16.6 on the TTOACS-5S-CG-1P to 110.2 on the TTOACS-40D-MZC-2P. Don't scale from tonnage, because the dual-zone units draw more than their single-zone neighbors for less rating. At the 30 size the TTOACS-30D-MZC-2P draws 92.8 amps for 27.7 tons, while the TTOACS-30S-CG-1P draws 82.3 for 28.8. At 40 it is 110.2 amps for 37.2 tons against 102.3 for 38.4. A feeder sized for the S model and later used for the D model at the same size comes up about 8 to 11 amps short, so settle the zone count before the electrician sizes the circuit.

Every rating shrinks to 0.40 of its 50°F figure, so a 10-ton load at 20°F needs a unit rated about 25 tons: the TTOACS-30S-CG-1P or TTOACS-30D-MZC-2P, at about 11.5 and 11.1 tons delivered. The TTOACS-25S-CG-1P looks right by name, but its 24.2-ton rating gives only about 9.7 tons at 20°F, a shortfall that shows up as a loop that never quite reaches setpoint. At a 20°F supply the glycol mix also has to protect well below the fluid temperature, and below the coldest outdoor night if that is colder still.

For most sites yes, though the pair has one real advantage: two separate packages survive a failure that would stop a single frame. On paper they are close. Two TTOACS-20S-CG-1P units total 37.8 tons and 104 full-load amps with 136 gallons of reservoir, against 37.2 tons, 110.2 amps and 200 gallons on the dual-zone TTOACS-40D-MZC-2P. The single D package means one pad, one power connection, one set of process lines through the wall and a larger tank for batch loads. The pair means two of everything, but a power fault, a control failure or a damaged frame takes out half the plant instead of all of it. Where a cellar can't lose its cooling at all, the pair, or a D model plus a spare, earns its extra installation.

Not as published: these units are listed for 20°F to 70°F supply fluid, so a 75°F or 80°F duty needs us to confirm the unit at that setpoint before it is quoted. Often the simpler route is to run the chiller at or below 70°F and let a mixing valve at the load blend return fluid in to lift the supply to what the process wants, which keeps the unit inside its published range.