An outdoor packaged chiller moves everything that makes noise and heat out of the building. The air-cooled condenser, the compressors, the reservoir and the pumps arrive as one package, set on a pad or a roof curb, and only the supply and return lines come through the wall. Inside, the process room loses no floor space and gains no heat.
The TTOACS units on this page run from 5.3 to 38.4 tons at 50°F. Eight are single-zone (the S models) and three are dual-zone, with two refrigeration zones (the D models, from 20.2 tons). All are published at 460V three-phase for 20°F to 70°F fluid, and are designed to run in ambient air from -20°F to 95°F.
The one voltage published in this rangeEvery TTOACS unit from 5.3 to 38.4 tons is three-phase at this voltage. A site with only 208V or 230V should say so before selection, since an indoor unit may be the simpler route.
Cold climates
Winter Is the Design Case
An outdoor loop runs glycol even at a 50°F setpoint.
The freeze point has to beat the coldest night, not the setpoint.
Designed to run from -20°F to 95°F.
Summer is when to check capacity.
Supply and return lines outside the building are insulated.
Every exposed section carries protected fluid.
| Part Number | Series | Tons (50°F) | Zones | Process Flow | Reservoir | Full Load Amps (460V) |
|---|---|---|---|---|---|---|
| TTOACS-5S-CG-1P | TTOACS | 5.3 | 1 | 12 GPM | 68 gal | 16.6 |
| TTOACS-7.5S-CG-1P | TTOACS | 7.8 | 1 | 18 GPM | 65 gal | 22.8 |
| TTOACS-10S-CG-1P | TTOACS | 10.2 | 1 | 24 GPM | 68 gal | 28.5 |
| TTOACS-15S-CG-1P | TTOACS | 14.4 | 1 | 36 GPM | 68 gal | 45.0 |
| TTOACS-20S-CG-1P | TTOACS | 18.9 | 1 | 48 GPM | 68 gal | 52.0 |
| TTOACS-20D-MZC-2P | TTOACS | 20.2 | 2 | 48 GPM | 150 gal | 59.2 |
| TTOACS-25S-CG-1P | TTOACS | 24.2 | 1 | 60 GPM | 100 gal | 67.9 |
| TTOACS-30D-MZC-2P | TTOACS | 27.7 | 2 | 72 GPM | 200 gal | 92.8 |
| TTOACS-30S-CG-1P | TTOACS | 28.8 | 1 | 72 GPM | 100 gal | 82.3 |
| TTOACS-40D-MZC-2P | TTOACS | 37.2 | 2 | 96 GPM | 200 gal | 110.2 |
| TTOACS-40S-CG-1P | TTOACS | 38.4 | 1 | 96 GPM | 100 gal | 102.3 |
Ratings at 50°F leaving water. Every model here is published at 460V three-phase.
Single- and dual-zone TTOACS units that put the whole refrigeration plant on a pad outside, rated to run from -20°F to 95°F ambient.
A single-zone unit is one refrigeration system on one tank. It is the right choice for a steady load with a planned maintenance window. A dual-zone unit carries two refrigeration zones: at part load one zone can carry the process, and a fault in one zone leaves the other running. For a brewery cellar or a food line that cannot stop for a compressor repair, the D models from 20.2 tons are the usual pick.
Model names round to a size class; the ratings do not. The TTOACS-40S-CG-1P is rated 38.4 tons and the TTOACS-30D-MZC-2P 27.7 tons at 50°F. Select from the rating in the table, then apply the multiplier for your setpoint: 38.4 tons at 50°F is about 23 tons at 30°F.
Single-zone outdoor units run to 55.1 tons and dual-zone units to 188 tons, on the 40 to 100 ton and 100 to 210 ton outdoor pages.
The other line we supply covers this range as well - see its outdoor glycol chillers on our sister chiller site.