Central systems for the whole plant loop

Request a Quote

One Loop for the Plant

Central systems for the whole plant loop: dairies, production breweries, food plants and multi-press molding floors.

From 40 tons up, a glycol chiller stops being equipment beside the process and becomes a utility: one central system feeding a header that serves every load in the building. Portables fall away in this range. What remains are central chillers with large tanks, chilling modules that add to an existing tank and pump station, and outdoor packaged plants.

Thirty-two of the Temptek units we supply are rated above 40 and up to 100 tons at 50°F: ten TTI central chillers, sixteen MA and MW modules and six outdoor TTOACS units. Most carry two or three refrigeration zones, so the plant keeps part of its capacity when one zone is down.

Indoor Plant or Outdoor Plant

Indoors, the TTI water-cooled chillers and MW modules reject heat to a cooling tower; they suit a plant that already runs tower water for other equipment and has a mechanical room to house them. Outdoors, the choice is a complete TTOACS package on a pad, or an indoor TTI air-cooled chiller or MA module with its condenser outside.

The tank matters more here than at small sizes. The TTI units in this range carry 340 or 1,200 gallons, which is what lets a central loop absorb a batch of warm product or a kettle dump without the supply temperature swinging. MA and MW modules carry no tank of their own and are sized against the plant's.

In This Range

Water-cooled central glycol chiller, representative unit

Indoor Central Plant Systems:

Water-Cooled Central and Modules

  • 13 part numbers
  • 46.4 to 100 tons
  • Tower or city water
Air-cooled central glycol chiller, representative unit

Outdoor Central & Remote Condenser Systems:

Outdoor Packages and Remote Condensers

  • 19 part numbers
  • 42.7 to 90 tons
  • Heat rejected outdoors

SERIES FROM 40 TO 100 TONS

SERIES FORMAT CONDENSER TANK & PUMP MODELS RATED TONS (50°F)
TTI Air-Cooled Central, remote condenser Remote Air-Cooled Included 5 50 - 90
TTI Water-Cooled Central Water-Cooled Included 5 50 - 100
MA Modules Chilling module Remote Air-Cooled Separate 8 46.4 - 90
MW Modules Chilling module Water-Cooled Separate 8 46.4 - 100
TTOACS Outdoor package Air-Cooled Included 6 42.7 - 84.6
46.4-100 tons
what one MA or MW module adds to a plant
1,200 gallons
TTI tank from the 80-ton models up
0.60
share of the 50°F rating left at 30°F
460V
published supply, outdoor TTOACS units

Selecting a Central System

Start from the plant's peak load at the coldest supply temperature any process needs, then decide how much of it must keep running with a zone or a unit down. Two 50-ton units on a common header cost more than one 100-ton unit and give a plant that never loses all its cooling at once; a single TTI-100W carries 100 tons on two zones in one frame.

Size the Tank With the Chiller

A central loop holds its supply temperature only if the tank and the chiller together can absorb the largest slug of heat the process delivers at once. As a check, 1,200 gallons of 30% propylene glycol warms about 1°F for every 9,500 BTU dumped into it, so a 90,000 BTU batch lifts the tank nearly 10°F before the chiller has done any work.

Tower water or air

Water-cooled central chillers give the steadiest capacity on the hottest day, because tower water follows the wet-bulb temperature rather than the dry-bulb. The cost is the tower, its water treatment and its winter protection. A plant without a tower usualy lands on the outdoor or remote-condenser side of this range.

Modules for plants that already have a pump tank

The MA and MW modules are the refrigeration section of a central chiller on their own frame. Where a plant already runs a pump tank and distribution pumps, a module adds 46.4 to 100 tons without replacing that equipment - and more modules can follow as the plant grows, which is how the 210+ ton plants are built.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

40 to 100 Ton Central Systems: Selection Notes

The smaller tank swings about three and a half times as far for the same slug of heat. Scaling this page's figure of roughly 9,500 BTU per °F for a 1,200-gallon tank holding a 30% propylene glycol mix, a 340-gallon tank takes about 2,700 BTU per °F. The 90,000 BTU batch that lifts the large tank under 10°F would push the small one up more than 30°F, enough to take a 30°F loop far above any useful supply temperature. In this range the 340-gallon tank comes on the TTI units up to 60 tons, so a plant with real batch loads below that size either steps up to an 80-ton frame or adds an external tank.

The top is 90 tons at 50°F from a TTI air-cooled chiller or an MA module, and 84.6 from the largest TTOACS package; only the water-cooled TTI and MW units reach 100. At a 30°F setpoint those top figures come to about 54 and 51 tons. A plant with no tower and a true 100-ton load at 50°F therfore needs a unit from the 100 to 210 ton range, or two units from this range on a header. Two TTOACS units can be the better answer anyway, since the plant keeps running on one of them.

About 50 tons, halfway between the published 0.60 at 30°F and 0.40 at 20°F. That halves every figure in the series table, so the largest water-cooled units here become 50-ton machines on a 25°F loop, and the 84.6-ton top outdoor package comes to about 42. Turned around, a 60-ton load held at 25°F calls for roughly 120 tons of 50°F rating, above anything listed on this page. Interpolating between published points is fine for planning; confirm the multiplier at your exact setpoint with us before the purchase order.

Everything except the outdoor TTOACS packages, which are published for 460V three-phase only. The TTI central chillers, air-cooled and water-cooled, and all sixteen MA and MW modules carry published ratings at all three voltages, 230V, 460V and 575V. So a 575V plant with no tower still has an air-rejected option: an indoor TTI air-cooled unit or MA module, rejecting through a remote condenser. Raise the voltage in the first conversation; a TTOACS chosen for its simple yard installation and only later checked against a 575V service means starting the selection over.

Anywhere from under 10 minutes to about an hour, because recovery runs only on the capacity left over after the steady load. At 30°F an 80-ton rating gives about 48 tons, or 576,000 BTU/hr. With nothing else on the loop, all of it goes at the slug and the 90,000 BTU is gone in a little over 9 minutes. With a steady 40-ton load already running, only 8 tons, 96,000 BTU/hr, is left over, and recovery takes close to an hour, with the 1,200-gallon tank sitting several degrees warm the whole time. Run this check whenever a batch process is added to an existing loop: a chiller can be large enough on paper and still leave the supply warm for an hour after every batch.