Zone means two different things in a large glycol plant, and both belong on this page. Inside a chiller, a refrigeration zone is a separate refrigeration system - its own compressors and circuit - so a two-zone unit carries two refrigeration systems in one package. Across a plant, a temperature zone is a loop held at its own setpoint by its own chiller or group of chillers.
The units here are the building blocks for both: eleven dual-zone TTOACS outdoor packages from 20.2 to 188 tons, and seven three-zone TTI central chillers from 85.5 to 180 tons, air-cooled through a remote condenser or water-cooled.
Rating behind 150 tons of 28°F loadA cold loop needs far more rating than load, which is why the example site gives it two TTOACS-150D packages plus a spare and keeps the 45°F process loop on its own chiller.
Example plant
A Two-Temperature Site
150 tons of load at 28°F needs about 270 tons of rating.
Two TTOACS-150D packages, plus one spare.
120 tons of load at 45°F needs about 135 tons of rating (x 0.90).
One three-zone TTI-150W.
Four units on two loops.
The cold loop survives a unit down, the process loop a zone down.
| Part Number | Series | Tons (50°F) | Condenser | Zones | Tank / Pump |
|---|---|---|---|---|---|
| TTI-90A | TTI Air-Cooled | 85.5 | Remote Air-Cooled | 3 | 1,200 gal / 270 GPM |
| TTI-150A | TTI Air-Cooled | 135 | Remote Air-Cooled | 3 | 1,200 gal / 450 GPM |
| TTI-180A | TTI Air-Cooled | 180 | Remote Air-Cooled | 3 | 1,200 gal / 540 GPM |
| TTI-90W | TTI Water-Cooled | 90 | Water-Cooled | 3 | 1,200 gal / 270 GPM |
| TTI-120W | TTI Water-Cooled | 127.8 | Water-Cooled | 3 | 1,200 gal / 360 GPM |
| TTI-150W | TTI Water-Cooled | 150 | Water-Cooled | 3 | 1,200 gal / 420 GPM |
| TTI-180W | TTI Water-Cooled | 180 | Water-Cooled | 3 | 1,200 gal / 540 GPM |
| TTOACS-20D-MZC-2P | TTOACS | 20.2 | Air-Cooled | 2 | 150 gal / 48 GPM |
| TTOACS-30D-MZC-2P | TTOACS | 27.7 | Air-Cooled | 2 | 200 gal / 72 GPM |
| TTOACS-40D-MZC-2P | TTOACS | 37.2 | Air-Cooled | 2 | 200 gal / 96 GPM |
| TTOACS-50D-MZC-2P | TTOACS | 48.4 | Air-Cooled | 2 | 200 gal / 120 GPM |
| TTOACS-60D-MZC-2P | TTOACS | 57.4 | Air-Cooled | 2 | 400 gal / 144 GPM |
| TTOACS-80D-MZC-2P | TTOACS | 75.8 | Air-Cooled | 2 | 400 gal / 192 GPM |
| TTOACS-100D-MZC-2P | TTOACS | 84.6 | Air-Cooled | 2 | 400 gal / 240 GPM |
| TTOACS-120D-MZC-2P | TTOACS | 110.1 | Air-Cooled | 2 | 400 gal / 288 GPM |
| TTOACS-150D-MZC-2P | TTOACS | 145.8 | Air-Cooled | 2 | 900 gal / 350 GPM |
| TTOACS-190D-MZC-2P | TTOACS | 170.1 | Air-Cooled | 2 | 900 gal / 451 GPM |
| TTOACS-210D-MZC-2P | TTOACS | 188 | Air-Cooled | 2 | 900 gal / 490 GPM |
Ratings at 50°F leaving water. TTI air-cooled units are listed without their remote condensers.
Units that split capacity across two or three refrigeration zones, and plants that run separate loops at separate temperatures.
Refrigeration zones inside a unit are the simplest redundancy a plant can buy: one frame, one tank, one set of process connections, and no single compressor fault that stops the loop. They do not protect against losing the whole unit - a power fault, or a failure both zones share. For a loop that cannot stop at all, the plant needs a second unit.
Three zones step capacity more finely, which helps where the load swings between day and night shifts, and they lose less when one zone is down. Two zones make a lighter, simpler unit. In the TTI range the choice is direct: the TTI-150W carries three zones and the TTI-150WD two, at 150 and 147 tons.
Two temperature loops can still share a mechanical room, a tower and a controls system. What they should not share is a chiller: a unit asked to serve a 28°F load and a 45°F load at once serves both at the colder setpoint, and at the colder setpoint's capacity.
The other line we supply covers this range as well - see its single- and dual-zone outdoor central chillers on our sister chiller site.