Dual-Zone & Multi-Zone Glycol Chillers

Capacity split across two or three refrigeration zones

Request a Quote

Zones Inside a Unit, Loops Across a Plant

TTOACS Dual-Zone and TTI Three-Zone Units

Zone means two different things in a large glycol plant, and both belong on this page. Inside a chiller, a refrigeration zone is a separate refrigeration system - its own compressors and circuit - so a two-zone unit carries two refrigeration systems in one package. Across a plant, a temperature zone is a loop held at its own setpoint by its own chiller or group of chillers.

The units here are the building blocks for both: eleven dual-zone TTOACS outdoor packages from 20.2 to 188 tons, and seven three-zone TTI central chillers from 85.5 to 180 tons, air-cooled through a remote condenser or water-cooled.

Outdoor packaged glycol chiller, representative unit

WHAT TO SPECIFY

  • Two zones: each carries about half the rating; at light load one runs and the other waits.
  • TTOACS D models, 20.2 to 188 tons.
  • Three zones: each carries about a third; losing one leaves about two thirds of the capacity.
  • TTI three-zone models, 85.5 to 180 tons, air-cooled with a remote condenser or water-cooled.
  • Separate setpoints: one loop per temperature, each with its own chiller or group.
  • A mixing valve can serve a warmer load from a colder loop; the reverse is not possible.
270 tons

Rating behind 150 tons of 28°F loadA cold loop needs far more rating than load, which is why the example site gives it two TTOACS-150D packages plus a spare and keeps the 45°F process loop on its own chiller.

Example plant

A Two-Temperature Site

1.

Cold loop


150 tons of load at 28°F needs about 270 tons of rating.

Two TTOACS-150D packages, plus one spare.

2.

Process loop


120 tons of load at 45°F needs about 135 tons of rating (x 0.90).

One three-zone TTI-150W.

3.

Result


Four units on two loops.

The cold loop survives a unit down, the process loop a zone down.

DUAL-ZONE AND THREE-ZONE UNITS

Part Number Series Tons (50°F) Condenser Zones Tank / Pump
TTI-90A TTI Air-Cooled 85.5 Remote Air-Cooled 3 1,200 gal / 270 GPM
TTI-150A TTI Air-Cooled 135 Remote Air-Cooled 3 1,200 gal / 450 GPM
TTI-180A TTI Air-Cooled 180 Remote Air-Cooled 3 1,200 gal / 540 GPM
TTI-90W TTI Water-Cooled 90 Water-Cooled 3 1,200 gal / 270 GPM
TTI-120W TTI Water-Cooled 127.8 Water-Cooled 3 1,200 gal / 360 GPM
TTI-150W TTI Water-Cooled 150 Water-Cooled 3 1,200 gal / 420 GPM
TTI-180W TTI Water-Cooled 180 Water-Cooled 3 1,200 gal / 540 GPM
TTOACS-20D-MZC-2P TTOACS 20.2 Air-Cooled 2 150 gal / 48 GPM
TTOACS-30D-MZC-2P TTOACS 27.7 Air-Cooled 2 200 gal / 72 GPM
TTOACS-40D-MZC-2P TTOACS 37.2 Air-Cooled 2 200 gal / 96 GPM
TTOACS-50D-MZC-2P TTOACS 48.4 Air-Cooled 2 200 gal / 120 GPM
TTOACS-60D-MZC-2P TTOACS 57.4 Air-Cooled 2 400 gal / 144 GPM
TTOACS-80D-MZC-2P TTOACS 75.8 Air-Cooled 2 400 gal / 192 GPM
TTOACS-100D-MZC-2P TTOACS 84.6 Air-Cooled 2 400 gal / 240 GPM
TTOACS-120D-MZC-2P TTOACS 110.1 Air-Cooled 2 400 gal / 288 GPM
TTOACS-150D-MZC-2P TTOACS 145.8 Air-Cooled 2 900 gal / 350 GPM
TTOACS-190D-MZC-2P TTOACS 170.1 Air-Cooled 2 900 gal / 451 GPM
TTOACS-210D-MZC-2P TTOACS 188 Air-Cooled 2 900 gal / 490 GPM

Ratings at 50°F leaving water. TTI air-cooled units are listed without their remote condensers.

Designing Around Zones

Units that split capacity across two or three refrigeration zones, and plants that run separate loops at separate temperatures.

Refrigeration zones inside a unit are the simplest redundancy a plant can buy: one frame, one tank, one set of process connections, and no single compressor fault that stops the loop. They do not protect against losing the whole unit - a power fault, or a failure both zones share. For a loop that cannot stop at all, the plant needs a second unit.

Two zones or three

Three zones step capacity more finely, which helps where the load swings between day and night shifts, and they lose less when one zone is down. Two zones make a lighter, simpler unit. In the TTI range the choice is direct: the TTI-150W carries three zones and the TTI-150WD two, at 150 and 147 tons.

Separate loops, shared plant

Two temperature loops can still share a mechanical room, a tower and a controls system. What they should not share is a chiller: a unit asked to serve a 28°F load and a 45°F load at once serves both at the colder setpoint, and at the colder setpoint's capacity.

The other line we supply covers this range as well - see its single- and dual-zone outdoor central chillers on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Zones and Loops: What Engineers Ask

Because zones can't cover a whole package going down, and two packages are needed just to carry the load. Two TTOACS-150D-MZC-2P units give 291.6 tons of rating, while 150 tons at 28°F requires about 270, so there is little slack. Lose one package to a power loss, or any fault common to both of its zones, and the survivor holds about 81 tons at 28°F, a little over half the load. With the third package in place, 291.6 tons are still running after that failure. Relying on zones instead of a spare would only protect against a single compressor or circuit fault, which is not the failure that stops a whole cold loop.

No. With one of its three zones out it holds about 90 tons at 45°F against a 120-ton load. At that setpoint the 150-ton rating becomes roughly 135 tons (x 0.90), and two thirds of that is about 90, so the process loop keeps running but warm until the zone is back. Two measures close the gap without another chiller: shed about 30 tons of the least critical process load during the repair, or temper colder fluid from the 28°F loop into the 45°F loop through a mixing valve, since the cold side's spare TTOACS-150D leaves it capacity to give. If neither suits the plant, the process loop needs a second unit of its own.

The 90-ton TTI three-zone units, at about 13 to 14 gallons per ton of rating from their 1,200-gallon tanks; among the outdoor packages the smaller ones run highest, about 7 gallons per ton on the TTOACS-20D, 30D and 60D. The spread is wide. The TTOACS-120D-MZC-2P carries 400 gallons for 110.1 tons, only about 3.6 per ton, while the TTOACS-150D-MZC-2P jumps to 900 gallons, about 6.2. The TTI-180A and TTI-180W come to about 6.7. Where a loop takes warm product in slugs, gallons per ton says more than either figure alone, and a unit near the bottom of that ranking may need an external tank added to the quote.

A TTI-180W steps in thirds of roughly 60 tons, while a TTOACS-210D-MZC-2P steps in halves of roughly 94 tons. The difference shows at light load. Take a night load of about 50 tons on a 50°F loop: one TTI zone covers it with little excess, while one TTOACS zone carries nearly twice what is needed, cycles more and lets the supply swing wider around setpoint. On a site where day and night loads differ sharply, that finer step is often worth more than the extra 8 tons of rating the outdoor package carries.