Single-phase power is the constraint that defines this page. Where a building has only 115V or 230V single-phase service - a laboratory, a brewpub, a winery tasting room, a pilot line in a leased unit - the CF series is the complete answer up to 1.5 tons: compressor, air-cooled condenser with its own fan, a 4-gallon reservoir and a small process pump in one cabinet 33 to 37 inches tall.
The four smallest models run on 115V, and three of them on 230V as well; the CF-1A and CF-1.5A are 230V only. All six are rated at 50°F leaving water at a 90°F design ambient, and all six are published with R-513A.
Largest single-phase unit, the CF-1.5AThat rating is at 50°F and falls at a glycol setpoint. Past it, the choices are two CF units on separate circuits or a three-phase CG portable starting at 2 tons.
Before you order
Three Numbers to Send
The leaving fluid temperature the load needs.
Below 48°F the loop needs glycol.
BTU/hr, or tank volume, start and final temperature and the time allowed.
We convert it to tons at your setpoint.
115V or 230V single-phase, and the breaker available.
That picks between the 115V and 230V models.
| Part Number | Series | Tons (50°F) | Process Flow | Reservoir | Voltage | Full Load Amps | Shipping Weight |
|---|---|---|---|---|---|---|---|
| CF-.25A | CF | 0.29 | 0.7 GPM | 4 gal | 115V / 230V | 13 (115V) / 7 (230V) | 220 lbs |
| CF-.33A | CF | 0.39 | 0.9 GPM | 4 gal | 115V | 15 | 220 lbs |
| CF-.5A | CF | 0.5 | 1.2 GPM | 4 gal | 115V / 230V | 17 (115V) / 9 (230V) | 220 lbs |
| CF-.75A | CF | 0.75 | 1.8 GPM | 4 gal | 115V / 230V | 21 (115V) / 11 (230V) | 265 lbs |
| CF-1A | CF | 1 | 2.4 GPM | 4 gal | 230V | 16.2 | 345 lbs |
| CF-1.5A | CF | 1.5 | 3.6 GPM | 4 gal | 230V | 20 | 350 lbs |
Ratings at 50°F leaving water and 90°F ambient. Flow is the built-in process pump's published flow. Each part number links to its full specification.
Six plug-in CF units from 0.29 to 1.5 tons for labs, brewpubs, tasting rooms and bench-scale process loops.
The range steps in small increments - 0.29, 0.39, 0.5, 0.75, 1 and 1.5 tons - so the usual mistake is not picking the wrong size but picking to the nameplate. A load that measures 0.4 ton at a 28°F glycol supply is not a CF-.5A duty: at that setpoint a 0.5-ton unit delivers well below its rating. Size from the capacity at your setpoint and step up a model when the numbers are close.
The four smallest CF models use hermetic reciprocating compressors and the CF-1A and CF-1.5A use scroll compressors. Both are sealed units; the practical difference is weight, at 345 and 350 lbs shipping for the scroll models against 220 to 265 lbs for the others.
Above 1.5 tons there is no single-phase unit in the range. The next step is the three-phase CG portables from 2 tons, or two CF units on separate circuits where three-phase power is not available and the load can be split between them.
The other line we supply covers this range as well - see its 1/4 to 1.5 ton portable chillers on our sister chiller site.