Three Indoor Formats in One Range

CG, CG-ARC and TTI Units, 5.1 to 40 Tons

Every unit on this page is a complete chiller - refrigeration, reservoir, process pump and controls in one frame - installed inside the building. What differs is how each one gets rid of heat and how big a tank it carries, and those two things decide which suits a given room.

The CG portables (7.2 to 29 tons air-cooled, 5.1 to 40 tons water-cooled) carry 25- or 65-gallon tanks and reject heat into the room or into water. The CG-ARC units (7.1 to 36.7 tons) are the same chiller with its condenser moved outside. The TTI central chillers (20.5 to 40 tons here) carry a 340-gallon tank and two refrigeration zones, air-cooled through a remote condenser or water-cooled.

Water-cooled portable glycol chiller, representative unit

WHAT TO SPECIFY

  • Heat rejection: into the room (CG air-cooled, rated at 95°F ambient), outdoors through refrigerant lines (CG-ARC and TTI air-cooled), or into tower or city water (CG and TTI water-cooled).
  • Water-cooled units need, for example, 32 GPM of 60°F city water or 63 GPM of 85°F tower water on the CG-20W.
  • Tank: 20 or 25 gallons up to about 10 tons, 65 gallons from 14.5 tons on the CG and CG-ARC units, 340 gallons on the TTI.
  • Pump: sized at about 2.4 GPM per ton - 18 GPM on the CGD-7.5A up to 98 GPM on the TTI-40A.
  • Remote condensers need a refrigerant line set between the indoor unit and the outdoor condenser, and the system is charged in the field.
  • Voltage: 230V, 460V or 575V three-phase on every unit here.
95°F

Room limit for an air-cooled CG unitAn air-cooled portable rejects the load plus its compressor heat into the space around it. If the cellar or press hall cannot stay under this, move the heat outdoors or into water.

Choosing the format

Where Should the Heat Go?

1.

Into the room


CG air-cooled - the simplest install.

The room must stay under 95°F at full load.

2.

Outdoors


CG-ARC or TTI air-cooled with a remote condenser.

Needs a refrigerant line set and a field charge.

3.

Into water


CG or TTI water-cooled.

Needs tower or city water and a drain.

INDOOR PACKAGED UNITS, 5 TO 40 TONS

Part Number Series Tons (50°F) Condenser Process Flow Reservoir Voltage
CGD-7.5A CG Air-Cooled 7.2 Air-Cooled 18 GPM 25 gal 230V / 460V / 575V
CGD-10A CG Air-Cooled 9.8 Air-Cooled 24 GPM 25 gal 230V / 460V / 575V
CG-15AB CG Air-Cooled 14.5 Air-Cooled 36 GPM 65 gal 230V / 460V / 575V
CG-15AF CG Air-Cooled 14.5 Air-Cooled 36 GPM 65 gal 230V / 460V / 575V
CG-15AFF CG Air-Cooled 14.5 Air-Cooled 36 GPM 65 gal 230V / 460V / 575V
CG-20AB CG Air-Cooled 19.3 Air-Cooled 48 GPM 65 gal 230V / 460V / 575V
CG-20AF CG Air-Cooled 19.3 Air-Cooled 48 GPM 65 gal 230V / 460V / 575V
CG-20AFF CG Air-Cooled 19.3 Air-Cooled 48 GPM 65 gal 230V / 460V / 575V
CG-25A CG Air-Cooled 24.5 Air-Cooled 60 GPM 65 gal 230V / 460V / 575V
CG-30A CG Air-Cooled 29 Air-Cooled 72 GPM 65 gal 230V / 460V / 575V
CGD-5W CG Water-Cooled 5.1 Water-Cooled 12 GPM 25 gal 230V / 460V / 575V
CG-7.5W CG Water-Cooled 7.6 Water-Cooled 19 GPM 25 gal 230V / 460V / 575V
CGD-10W CG Water-Cooled 10.6 Water-Cooled 26 GPM 25 gal 230V / 460V / 575V
CGD-15W CG Water-Cooled 15 Water-Cooled 36 GPM 65 gal 230V / 460V / 575V
CG-20W CG Water-Cooled 20 Water-Cooled 48 GPM 65 gal 230V / 460V / 575V
CG-25W CG Water-Cooled 26 Water-Cooled 60 GPM 65 gal 230V / 460V / 575V
CG-30W CG Water-Cooled 30 Water-Cooled 72 GPM 65 gal 230V / 460V / 575V
CG-40W CG Water-Cooled 40 Water-Cooled 92 GPM 65 gal 230V / 460V / 575V
CG-7.5A-RC CG-ARC 7.1 Remote Air-Cooled 19 GPM 20 gal 230V / 460V / 575V
CGD-10A-RC CG-ARC 9.8 Remote Air-Cooled 26 GPM 25 gal 230V / 460V / 575V
CGD-15A-RC CG-ARC 14.5 Remote Air-Cooled 36 GPM 65 gal 230V / 460V / 575V
CG-20A-RC CG-ARC 18.5 Remote Air-Cooled 48 GPM 65 gal 230V / 460V / 575V
CG-25A-RC CG-ARC 23.1 Remote Air-Cooled 60 GPM 65 gal 230V / 460V / 575V
CG-30A-RC CG-ARC 30 Remote Air-Cooled 72 GPM 65 gal 230V / 460V / 575V
CG-40A-RC CG-ARC 36.7 Remote Air-Cooled 92 GPM 65 gal 230V / 460V / 575V
TTI-20A TTI Air-Cooled 20.5 Remote Air-Cooled 48 GPM 340 gal 230V / 460V / 575V
TTI-30A TTI Air-Cooled 28.5 Remote Air-Cooled 72 GPM 340 gal 230V / 460V / 575V
TTI-40A TTI Air-Cooled 40 Remote Air-Cooled 98 GPM 340 gal 230V / 460V / 575V
TTI-20W TTI Water-Cooled 20.5 Water-Cooled 48 GPM 340 gal 230V / 460V / 575V
TTI-30W TTI Water-Cooled 30 Water-Cooled 72 GPM 340 gal 230V / 460V / 575V
TTI-40W TTI Water-Cooled 40 Water-Cooled 96 GPM 340 gal 230V / 460V / 575V

Ratings at 50°F leaving water; air-cooled CG ratings at 95°F ambient. Remote-condenser units are listed with the indoor chiller's tank and pump.

Portable, Remote or Central?

Portables, remote-condenser chillers and small central units with the tank and pump built in, for cellars, press rooms and process halls.

A portable CG unit is the least installation: set it down, pipe supply and return to the load, connect power. It suits one or two process points close to the unit. Its limit is the room. A 20-ton air-cooled unit rejects more than 20 tons of heat - the load plus its compressors - and a cellar or a press hall has to absorb that without climbing past 95°F.

When the room cannot take the heat

The CG-ARC units keep the chiller indoors and move only the condenser outside, so the room sees the chiller's cabinet and pump but not the rejected heat. They add a refrigerant line set and a field charge, and the condenser needs a pad or roof curb within the line length the installer can support.

When the load is several points on one loop

The TTI central chillers exist for a loop that feeds a header: a cellar of fermenters, a row of presses. Their 340-gallon tank smooths the swings when a batch dumps heat into the loop, and two refrigeration zones give two capacity steps and keep part of the capacity running if one zone is down. For the same duty outdoors, see the outdoor packaged units.

The other line we supply covers this range as well - see its 20 to 40 ton portable chillers on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Indoor Packaged Units: Installation Questions

The water-cooled versions rate a little higher, and the remote-condenser versions match or fall slightly below the air-cooled ones. At the 25 size, for example, the CG-25W is rated 26 tons, the CG-25A 24.5 and the CG-25A-RC 23.1. At 20 the order holds: the CG-20W at 20, the CG-20A models at 19.3, the CG-20A-RC at 18.5. The CG-30A-RC is the exception, at 30 tons against 29 for the CG-30A. Select from the rated column, not the size in the name, especially on the remote units, where the gap reaches about 1.4 tons at the 25 size.

Four: the CG-40W and TTI-40W on water, and the TTI-40A and the 36.7-ton CG-40A-RC with remote condensers; no air-cooled CG portable comes this large. The CG-40W rates 40 tons with a 65-gallon tank and a 92 GPM pump, and needs tower or city water. The TTI-40W also rates 40 on water but brings a 340-gallon tank, a 96 GPM pump and two zones. The TTI-40A matches that on remote air with a 98 GPM pump. The CG-40A-RC carries 36.7 tons, so a load that truly needs 40 at 50°F goes to one of the other three. For both remote units, budget the field-installed refrigerant piping and the on-site charge.

About 10°F at full load: a ton is 12,000 BTU/hr, and at roughly 2.4 GPM per ton the water-side formula gives a 10°F rise. The table bears that out. The CG-30W moves 72 GPM at 30 tons, exactly 10°F, and the TTI-40A's 98 GPM at 40 tons is about 9.8°F. A process designed for a tighter rise needs more flow than the built-in pump supplies. A 20-ton load that must hold a 5°F rise needs 96 GPM, twice the 48 GPM on the CG-20W, so the answer is a secondary pump loop or a booster sized to that duty, not a bigger chiller.

A tank about five times larger and a second refrigeration zone, for the same 48 GPM pump and essentially the same rating, 20.5 tons against 20. The 340-gallon TTI tank against the 65-gallon CG tank is what lets a cellar absorb a warm transfer or a CIP return without the supply jumping. The second zone means a compressor fault leaves about half the capacity running. The CG-20W's advantage is the lighter installation: set it, pipe it, power it.

Only one unit sits right at that size, the water-cooled CGD-5W at 5.1 tons, and it leaves almost no margin above 5. Air-cooled options begin at 7.2 tons with the CGD-7.5A, and the remote-condenser line at 7.1 tons with the CG-7.5A-RC, so an air-cooled 5.5-ton duty lands on a unit about 30% larger then the load. That margin isn't wasted: it covers a colder setpoint than planned, and the 18 or 19 GPM pump gives a tighter rise than the 12 GPM on the CGD-5W. If the load really is 5 tons at 50°F with water on hand, the CGD-5W is the efficient pick.