1-805-484-2992

Quotes - Sizing - Sales

Glycol Chillers Under 5 Tons

Bench-top, lab, tasting-room and single-press loads

Request a Quote

Small Loads, Complete Units

Bench-top, lab, tasting-room and single-press loads: fractional plug-in units and three-phase portables, each with its own tank and pump.

Below 5 tons almost every glycol chiller we supply is a self-contained portable: compressor, condenser, reservoir, process pump and controls in one cabinet, delivered ready to pipe to the load. The decision in this range is rarely the format. It is the electrical supply the unit has to run on, the leaving temperature it has to hold, and whether the room it sits in can absorb the heat it rejects.

We supply the Temptek line new, and thirteen of its published part numbers fall under 5 tons at the 50°F rating point: six single-phase CF units from 0.29 to 1.5 tons, six three-phase CG portables from 2 to 4.9 tons (four air-cooled, two water-cooled), and one indoor chiller with a remote condenser, the CGD-5A-RC.

Where the Line Falls at 1.5 Tons

The split in this range is electrical before it is thermal. Every unit up to 1.5 tons runs on single-phase power - 115V on the four smallest CF models, 230V on the CF-1A and CF-1.5A - so it can go wherever a suitable branch circuit can be run. From 2 tons up the CG portables need three-phase power at 230V or 460V, and from 4 tons 575V is offered as well. A site with no three-phase service tops out at 1.5 tons from a single chiller.

Setpoint is the second filter. Every model is rated at 50°F leaving water, and capacity falls below that. The central and outdoor units in the larger ranges publish the multipliers - 0.80 at 40°F, 0.60 at 30°F, 0.40 at 20°F - and the portables lose capacity below 50°F in the same direction. We confirm the rating at your setpoint before quoting, so size from the setpoint, not the nameplate.

In This Range

Fractional-ton portable glycol chiller, representative unit

Single-Phase Portable:

115V and 230V, 0.29 to 1.5 Tons

  • 6 part numbers, CF Series
  • 4-gallon tank, 0.7 to 3.6 GPM
  • 220 to 350 lbs shipping
Air-cooled portable glycol chiller, representative unit

Three-Phase Portable:

230V to 575V, 2 to 4.9 Tons

  • 6 part numbers, CG Series
  • Air-cooled or water-cooled
  • 7.5- to 25-gallon tank

SERIES UNDER 5 TONS

SERIES FORMAT CONDENSER TANK & PUMP MODELS RATED TONS (50°F)
CF Portable Air-Cooled Included 6 0.29 - 1.5
CG Air-Cooled Portable Air-Cooled Included 4 2 - 4.9
CG Water-Cooled Portable Water-Cooled Included 2 2 - 3
CG-ARC Indoor, remote condenser Remote Air-Cooled Included 1 4.9
1.5 tons
ceiling on single-phase power
2.4 GPM
built-in pump flow per ton
48°F
lowest leaving temperature without glycol
0.29 ton
rating of the smallest CF model

Sizing a Small Glycol Load

Small loads are easy to under-size because each one looks trivial on its own, so add them up. A jacketed 7-barrel fermenter crashing from 68°F to 34°F over 24 hours sheds about 2,600 BTU/hr of sensible heat - roughly a fifth of a ton. A cellar of six of them crashing on the same day is over a ton, before the glycol lines, a warm tasting-room ambient and active fermentation on the other tanks are counted.

A Ton Is 24 GPM-Degrees

With water, one ton of cooling is 24 gallons per minute through a 1°F temperature change - or 2.4 GPM through 10°F. That is why the pumps on these units are sized at about 2.4 GPM per ton: a CF-1A moves 2.4 GPM and a CGD-5A 12 GPM. A load that needs a much tighter temperature rise than 10°F needs more flow than the built-in pump gives, and that changes the selection.

Check the room, not just the load

Every air-cooled unit in this range rejects its heat into the room it stands in - the load plus the compressor's own power. CF units are rated at 90°F ambient and the CG portables at 95°F, with 60°F as the minimum recommended ambient for both. A closet with no ventilation can pass 95°F within hours of start-up, and the chiller loses capacity just when the load peaks. Where the room cannot take the heat, the water-cooled CG-2W and CG-3W move it into plant or tower water instead.

Glycol protects the loop; it does not add capacity

The minimum recommended leaving temperature without glycol is 48°F. Below that the loop needs an inhibited glycol mix with a freeze point at least 10°F below the coldest fluid temperature it will see - propylene for food and beverage, ethylene where toxicity is not a concern. Glycol carries a little less heat per gallon than water, so the flow and the chiller are both checked at the mix you choose; the glycol type and mix guide covers the choice.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Small Glycol Loads: What to Know Before Sizing

Only the four smallest CF units are 115V, and even they need a dedicated circuit sized to their nameplate rather than a receptacle shared with other equipment. They draw 13 to 21 full-load amps at 115V. The CF-1A and CF-1.5A move to 230V single-phase, which means a dedicated branch circuit, not an office outlet, and above 1.5 tons every unit here is three-phase. The usual surprise comes after delivery, when a unit is plugged into the nearest receptacle and the breaker opens during the first pull-down, so plan the circuit before the chiller arrives.

Only on paper at 50°F, and not with enough margin to count on at a crash setpoint. The 7-barrel crash on this page runs about 2,600 BTU/hr against the CF-.25A's roughly 3,500 BTU/hr at 50°F, but taking a tank down to 34°F needs supply fluid well below 50°F, where the CF rating falls. The CF pages publish no setpoint multiplier, so the unit's capacity at your setpoint is checked before we quote, and a 900 BTU/hr cushion at the 50°F point is thin to start with. It also leaves nothing for line gains or a second vessel. The 1-ton CF-1A starts at more than four times the crash load at 50°F, which leaves real room for the derate, and its rating at your setpoint is confirmed with the quote. For a cellar of several 7-barrel tanks crashing the same week, the three-phase CG portables are the realistic floor.

Only the CGD-5A-RC, a 4.9-ton indoor chiller whose condenser sits outdoors at the end of a refrigerant line set. Every other air-cooled unit in this range, the six CF models and the four air-cooled CG portables, puts the load and its own compressor heat into the surrounding space. Below about 4.9 tons, the alternatives for a hot or closed room are the water-cooled CG-2W and CG-3W, which need city or tower water, or moving the chiller to a better-ventilated space and running longer process lines to the load.

Once the combined load at your setpoint approaches about 4 tons, or as soon as a second or third small chiller is being considered for the same room. At that point one larger unit on a shared loop usualy means less equiptment to maintain and one electrical feed instead of several, and it leaves room for the next tank. Small loads hide this: six 7-barrel fermenters crashing on the same day already pass a ton before lines and fermentation heat are counted, and a brewpub that adds tanks every year reaches the top of this range sooner than its first sizing suggested. Remember that the ceiling here is a 50°F figure. No multiplier is published for the CF and CG portables, but they deliver less on a glycol setpoint, so we check the 4.9-ton CGD-5A at your setpoint, and a load near 4 tons on a cold loop has often outgrown this range already.

Not below 60°F, the minimum recommended ambient for both the CF and the air-cooled CG units. An unheated loading dock, a garage bay or a winter warehouse can fall well under that overnight, and a chiller running below its minimum ambient loses stable head pressure and control. Keep the unit in a space held above 60°F year-round, or move it to a conditioned room and run longer process lines to the load.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales