Past 100 tons an indoor central plant is a mechanical-room installation with its own tower loop, its own power feed and its own maintenance schedule. The units here are the heaviest in the line we supply: a TTI-180W ships at 10,500 lbs with its tank.
The TTI water-cooled chillers run from 120 to 180 tons, each with a 1,200-gallon tank and a 360 to 540 GPM process pump. Three are dual-zone WD models (TTI-120WD, TTI-150WD and TTI-180WD) and three carry three zones (TTI-120W, TTI-150W and TTI-180W). The MW modules run from 103 to 180 tons on two or three circuits.
Tower water the TTI-180WD calls forThe tower has to carry the load plus the compressor heat, and it runs whenever the plant runs. As 60°F city water the same duty takes about half the flow, 267 GPM on this model.
Plant uptime
Losing One Zone
One down leaves about half the rating.
TTI WD models, MW CC modules.
One down leaves about two thirds.
TTI W models, MW CCC modules.
One down leaves the other unit's full rating.
The plant-wide approach.
| Part Number | Series | Tons (50°F) | Zones | Tank / Pump | Voltage |
|---|---|---|---|---|---|
| TTI-120WD | TTI Water-Cooled | 120 | 2 | 1,200 gal / 360 GPM | 230V / 460V / 575V |
| TTI-120W | TTI Water-Cooled | 127.8 | 3 | 1,200 gal / 360 GPM | 230V / 460V / 575V |
| TTI-150WD | TTI Water-Cooled | 147 | 2 | 1,200 gal / 360 GPM | 230V / 460V / 575V |
| TTI-150W | TTI Water-Cooled | 150 | 3 | 1,200 gal / 420 GPM | 230V / 460V / 575V |
| TTI-180WD | TTI Water-Cooled | 178 | 2 | 1,200 gal / 432 GPM | 230V / 460V / 575V |
| TTI-180W | TTI Water-Cooled | 180 | 3 | 1,200 gal / 540 GPM | 230V / 460V / 575V |
| MW-105-CCC | MW Modules | 103 | 3 | Separate | 230V / 460V / 575V |
| MW-120-CC | MW Modules | 120 | 2 | Separate | 230V / 460V / 575V |
| MW-120-CCC | MW Modules | 120 | 3 | Separate | 230V / 460V / 575V |
| MW-150-CCC | MW Modules | 135 | 3 | Separate | 230V / 460V / 575V |
| MW-180-CCC | MW Modules | 180 | 3 | Separate | 230V / 460V / 575V |
Figures are rated at 50°F leaving water, and the MW modules rely on a separate reservoir and pumping system.
Tower-water plants from 103 to 180 tons: TTI central chillers with their own 1,200-gallon tanks, and MW modules for existing pump stations.
The TTI-150WD and TTI-150W are both about 150 tons - 147 and 150 at 50°F. The WD splits that across two refrigeration zones and ships 2,600 lbs lighter; the W splits it across three, so each zone is smaller and the loss of one takes less away. A plant that runs near full load around the clock usually prefers three zones.
Most units here are published with R-454B. The TTI-150WD and TTI-180WD are published with R-513A, the TTI-180W with R-410A and the MW-105-CCC with R-407C. The refrigerant effects service practice and future availability, so it belongs in the specification.
Where a plant already has a pump tank station feeding its header, MW modules add capacity without a second tank: an MW-120-CCC adds 120 tons on three circuits at 3,600 lbs, against 8,600 lbs for a TTI-120W with its own tank and pump. The plant-wide systems page shows how modules build a plant past 210 tons.
The other line we supply covers this range as well - see its water-cooled chilling modules, 5 to 180 tons on our sister chiller site.
Call and talk it through with an engineer: 1-805-484-2992