Tower-water plants from 103 to 180 tons

Request a Quote

Tower-Water Plants at Full Scale

TTI Water-Cooled and MW Modules, 103 to 180 Tons

Past 100 tons an indoor central plant is a mechanical-room installation with its own tower loop, its own power feed and its own maintenance schedule. The units here are the heaviest in the line we supply: a TTI-180W ships at 10,500 lbs with its tank.

The TTI water-cooled chillers run from 120 to 180 tons, each with a 1,200-gallon tank and a 360 to 540 GPM process pump. Three are dual-zone WD models (TTI-120WD, TTI-150WD and TTI-180WD) and three carry three zones (TTI-120W, TTI-150W and TTI-180W). The MW modules run from 103 to 180 tons on two or three circuits.

Water-cooled chilling module, representative unit

WHAT TO SPECIFY

  • Tower water: 346 GPM of 85°F tower water on the TTI-120WD up to 534 GPM on the TTI-180WD; about half that as 60°F city water.
  • The tower is sized for the load plus the compressor heat, and it runs whenever the plant runs.
  • Dual-zone or three-zone: the WD models split capacity in two, the W models in three.
  • The WD models are lighter: 7,500 lbs for the TTI-180WD against 10,500 lbs for the TTI-180W.
  • Modules: the MW units carry no tank or process pump, ship at 3,450 to 4,200 lbs and connect to the plant's pump station.
  • Voltage: 230V, 460V or 575V three-phase.
534 GPM

Tower water the TTI-180WD calls forThe tower has to carry the load plus the compressor heat, and it runs whenever the plant runs. As 60°F city water the same duty takes about half the flow, 267 GPM on this model.

Plant uptime

Losing One Zone

1.

Two zones


One down leaves about half the rating.

TTI WD models, MW CC modules.

2.

Three zones


One down leaves about two thirds.

TTI W models, MW CCC modules.

3.

Two units


One down leaves the other unit's full rating.

The plant-wide approach.

INDOOR CENTRAL SYSTEMS, 100 TO 210 TONS

Part Number Series Tons (50°F) Zones Tank / Pump Voltage
TTI-120WD TTI Water-Cooled 120 2 1,200 gal / 360 GPM 230V / 460V / 575V
TTI-120W TTI Water-Cooled 127.8 3 1,200 gal / 360 GPM 230V / 460V / 575V
TTI-150WD TTI Water-Cooled 147 2 1,200 gal / 360 GPM 230V / 460V / 575V
TTI-150W TTI Water-Cooled 150 3 1,200 gal / 420 GPM 230V / 460V / 575V
TTI-180WD TTI Water-Cooled 178 2 1,200 gal / 432 GPM 230V / 460V / 575V
TTI-180W TTI Water-Cooled 180 3 1,200 gal / 540 GPM 230V / 460V / 575V
MW-105-CCC MW Modules 103 3 Separate 230V / 460V / 575V
MW-120-CC MW Modules 120 2 Separate 230V / 460V / 575V
MW-120-CCC MW Modules 120 3 Separate 230V / 460V / 575V
MW-150-CCC MW Modules 135 3 Separate 230V / 460V / 575V
MW-180-CCC MW Modules 180 3 Separate 230V / 460V / 575V

Figures are rated at 50°F leaving water, and the MW modules rely on a separate reservoir and pumping system.

WD or W: Two Zones or Three

Tower-water plants from 103 to 180 tons: TTI central chillers with their own 1,200-gallon tanks, and MW modules for existing pump stations.

The TTI-150WD and TTI-150W are both about 150 tons - 147 and 150 at 50°F. The WD splits that across two refrigeration zones and ships 2,600 lbs lighter; the W splits it across three, so each zone is smaller and the loss of one takes less away. A plant that runs near full load around the clock usually prefers three zones.

Refrigerants

Most units here are published with R-454B. The TTI-150WD and TTI-180WD are published with R-513A, the TTI-180W with R-410A and the MW-105-CCC with R-407C. The refrigerant effects service practice and future availability, so it belongs in the specification.

Adding modules to an existing plant

Where a plant already has a pump tank station feeding its header, MW modules add capacity without a second tank: an MW-120-CCC adds 120 tons on three circuits at 3,600 lbs, against 8,600 lbs for a TTI-120W with its own tank and pump. The plant-wide systems page shows how modules build a plant past 210 tons.

The other line we supply covers this range as well - see its water-cooled chilling modules, 5 to 180 tons on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Before You Order a Tower-Water Central Plant

About 16,000 gallons an hour at full load, from the published 267 GPM of 60°F city water on this model. Over a 24-hour production day that comes to roughly 384,000 gallons, and the TTI-180W at 259 GPM is close behind. Few plants can buy or discharge that much water, which is why city water at this size works as a stopgap while a tower is down, not as the design. If a tower outage is a real risk, plan the valving and the drain capacity for it ahead of time; discovering mid-outage that the drain can't take 267 GPM costs the day.

The refrigerant, the pump and the weight. The TTI-150WD is published with R-513A and the TTI-150W with R-454B, which matters to a plant that standardizes its service work on one refrigerant. The W carries a 420 GPM pump against 360 on the WD, so at full load the W runs about an 8.6°F rise across the process and the WD about 9.8°F. The WD also ships 2,600 lbs lighter. Rating barely moves, 147 tons against 150, and both carry 1,200-gallon tanks. Where the plant runs hard all day, the third zone usually settles it; where rigging or floor loading is the constraint, the lighter WD often wins.

The larger pump keeps the full-load rise through the process narrower. By the water-side formula, 180 tons at 540 GPM is about an 8°F rise, while 178 tons at 432 GPM is close to 10°F. A glycol mix carries slightly less heat per gallon than plain water, so the real rise runs a little higher on both. The tower side runs the other way: the TTI-180W draws 518 GPM of 85°F water and the TTI-180WD 534. Choose the pump to suit the process, not the cabinet. Plate exchangers and jacketed tanks designed for a tight rise need the flow, while a loop content at 10°F gains nothing from the extra pumping power.

MW modules, by a wide margin: each weighs between 3,450 and 4,200 lbs shipped and holds almost no fluid, while the TTI-180W leaves the factory at 10,500 lbs and then takes on 1,200 gallons of glycol mix. On a water basis that fill is roughly another 10,000 lbs on the same footprint. The dual-zone TTI-180WD comes in at 7,500 lbs, and the TTI-120W at 8,600. With modules the fluid sits in the plant's own tank, so the load spreads over two locations. On an upper floor or an older slab, that difference can decide between a TTI and modules before any thermal question comes up, so get the structural check done early.