If the old unit's data plate is gone, illegible, or from a discontinued line, your process numbers get you to a rating just as reliably.
When a model match isn't available - the nameplate is gone, the brand is discontinued, or the unit predates readily available spec data - sizing from your actual current process is just as accurate as matching an old model number, and it has one real advantage: it reflects your process today rather than whatever it needed when the original unit was installed, which may have changed.
The inputs are the same ones covered in How to Size a Glycol Chiller under Sizing & Selection Guides - heat load, target leaving fluid temperature, and indoor-vs-outdoor installation. If you can measure or estimate those directly from your current operation, you don't need the old unit's spec sheet at all.
Send us what you have - even a rough sense of tank volume, process type, and how the old chiller performed (comfortably, marginally, or struggling) - and we can work toward a sizing recommendation from there, filling in the gaps with the same engineering approach we'd use for a brand-new installation.
How the old unit held setpoint through the hardest part of the year says more than its badge. Size to the fastest cooldown you run, with a real match to that peak instead of a cautious oversize.
Start with what the old unit actually did, not what its badge said. A chiller that comfortably held setpoint through the worst part of the year was almost certainly sized with margin above the true peak load - a struggling unit was likely undersized, marginal, or has lost capacity with age. Either read is more useful for sizing a replacement than a faded tonnage number.
The most common mistake here is sizing off an average operating condition instead of the worst-case one. A tank that's cooled twice a day needs capacity for the fastest cooldown you actually run, not the slower ones - undersizing on the peak is the single most common reason a "correctly sized" replacement still falls short.
Oversizing has its own cost, even though it feels like the safer error. A packaged unit running well below its rated load cycles more often and spends more time at inefficient part-load operation, which shows up as higher energy cost and more wear on the compressor over the unit's life than a properly matched unit would carry. The goal is a real match to the peak, not a large margin added out of caution.
| Duty Type | Typical Leaving Fluid Temp | Typical Install |
|---|---|---|
| Brewery / distillery fermentation | 25-30°F | Portable or small packaged, indoor or outdoor |
| Dairy / food & beverage process | 28-38°F | Portable through packaged central |
| General industrial process cooling | 40-55°F | Portable through packaged central, indoor or outdoor |
| Comfort-adjacent / equipment cooling | 45-65°F | Packaged central, typically outdoor |
These are starting points to sanity-check your numbers against, not a substitute for sizing to your actual load.