Glycol Type & Mix

Propylene vs. Ethylene, and Setting the Right Percentage

Overview

The wrong glycol type or a mix percentage set by guesswork are two of the most common - and most avoidable - problems we see in the field.

Propylene glycol is the standard choice anywhere the fluid could contact product or a food-safe environment matters - it's the food-grade option used across brewing, dairy, food processing and most commercial applications. Ethylene glycol offers marginally better heat transfer and is common in fully closed industrial or HVAC loops with no food-contact risk, but it's toxic and inappropriate anywhere a leak or cross-contamination could reach product or people.

Mix percentage is set by the coldest temperature the loop needs to survive - not a default like 25% or 30% applied everywhere. A 25% propylene glycol mix protects down to roughly 15°F before freezing risk; a 40% mix pushes that down to roughly -6°F, and about 44% is needed for -10°F. Under-mixing an outdoor or cold-climate loop risks a freeze-up; over-mixing an indoor loop needlessly reduces heat transfer efficiency and adds cost.

Mix percentage also affects the specific heat factor used in sizing (see How to Size a Glycol Chiller) - a richer mix moves slightly less heat per gallon than a leaner one, which is a real factor in flow-rate calculations, not just freeze protection.

  • Propylene glycol: the food-safe standard for anywhere product contact is a risk
  • Ethylene glycol: marginally better heat transfer, but toxic - closed industrial loops only
  • Mix percentage is set by the coldest temperature the loop must survive, not a default ratio
1

Screen for contact

Any product-contact risk means food-grade propylene

2

Find the design low

The coldest temperature the loop has to survive

3

Set the percentage

25% for roughly 15°F, about 44% for -10°F

4

Verify in the field

A refractometer reads the real mix from a sample

Choosing Type and Setting the Percentage

Glycol type is a food-safety decision first: food-grade propylene glycol anywhere the fluid could contact product, or where a leak into a food-safe environment is a real risk; industrial ethylene glycol only in fully closed, non-food-contact loops where its slightly better heat transfer is worth the toxicity trade-off.

Mix percentage is a separate decision, set by the coldest temperature the loop has to survive - not a default number carried over from another job. Under-mixing an outdoor or cold-climate loop risks a freeze-up; over-mixing an indoor loop needlessly cuts heat transfer efficiency and adds cost for protection the loop doesn't need.

Send Us

  • Whether the loop has any food/beverage or product-contact exposure
  • Coldest ambient or process temperture the loop must survive
  • Indoor or outdoor installation
  • Target leaving fluid temperature
  • Whether an existing loop's current mix percentage is known or needs testing

MIX PERCENTAGE VS. FREEZE PROTECTION

Propylene Glycol MixProtects Down ToTypical Use
25%Roughly 15°FIndoor, mild-climate outdoor duty
30-35%Roughly 9°F (30%) to 2°F (35%)Cold-climate outdoor, moderate process LFT
40%+Roughly -6°F at 40%, -10°F at about 44%Severe cold-climate outdoor installations

Figures are typical starting points for propylene glycol - confirm your actual mix against your site's design low temperature and process LFT together.
Call and talk it through with an engineer: 1-805-484-2992.

Propylene or Ethylene: Glycol Mix Questions

Any credible path for the fluid to reach product, a product-contact surface or a food-safe area, including leaks, maintenance and failures, not only normal operation. That covers jackets on fermenters, tanks and kettles, plate exchangers with glycol on one side and product on the other, and piping that runs over open product or through processing rooms. A spill during a pump change or a drain-down in a food area counts too. Ethylene only belongs where none of those paths exist, such as a sealed industrial loop well away from product. When in doubt, the answer is propylene.

Avoid it. Once any ethylene is in the loop it can no longer be treated as food-safe, which defeats the reason for running propylene. A blended fluid is also harder to verify, because the refractometer reading for concentration is interpreted for one glycol type, so a mixture reads true for neither. If an existing loop holds an unknown fluid, test it, and if there is doubt, drain, flush and refill with a single type at the target percentage before the new chiller starts.

Set it to whichever is colder, with margin, because the loop has to survive both. Take an indoor loop held at a 25°F leaving fluid temperture: a 25% propylene mix protects to roughly 15°F, only about 10°F below the setpoint, and the evaporator surface sits below the leaving fluid temperature, so that pairing is confirmed rather than assumed. Run the same loop's piping or chiller outdoors where winters drop well below 15°F, and the winter low takes over and the mix steps up the table. The process did not change but the fluid did, and the flow calculation then has to use the richer mix's lower heat-carrying capacity.

Toward the richer side, since the protection figures are approximate and the loop should not sit at its limit on the coldest night. A site with a 15°F design low lands exactly on the 25% row's roughly 15°F figure, so 25% leaves no margin and moving toward 30% buys some. The same logic holds at -10°F: a 40% mix only reaches about -6°F, so a site that cold needs roughly 44% or more, with the exact percentage confirmed for that design low when we quote. Each step richer gives up some heat transfer, so go one step, not two.