Three-Phase Portable Glycol Chillers

Six CG portables from 2 to 4.9 tons on three-phase power

Request a Quote

Three-Phase Portables, 2 to 4.9 Tons

CG Series, Air- and Water-Cooled

Once a site has three-phase power, a portable chiller can grow to 5 tons without leaving the single-cabinet format. The CG units on this page carry the same arrangement as the smaller CF series - compressor, condenser, reservoir, process pump and controls together - with a bigger tank, a pump sized at about 2.4 GPM per ton, and a choice of air-cooled or water-cooled condensers.

Four are air-cooled (the CG-2A, CG-3A, CG-4A and CGD-5A) and two water-cooled (the CG-2W and CG-3W). The 2- and 3-ton air-cooled units run on 230V or 460V; the rest add 575V. All six are rated at 50°F leaving water.

Air-cooled portable glycol chiller, representative unit

WHAT TO SPECIFY

  • Voltage: 230V or 460V on the CG-2A and CG-3A; 230V, 460V or 575V on the other four.
  • Full-load amps at 460V run from 8 on the CG-2W to 17 on the CGD-5A - size the feeder and disconnect from those figures.
  • Condenser: the air-cooled units are rated at 95°F ambient and put their heat into the room; the water-cooled units need city or tower water.
  • The CG-2W takes 3 GPM of 60°F city water or 6 GPM of 85°F tower water; the CG-3W 4.5 or 9 GPM.
  • Tank: 7.5 gallons up to 3 tons, 25 gallons on the CG-4A and CGD-5A.
  • Refrigerant: R-513A on the 2- and 3-ton units, R-454B on the CG-4A and CGD-5A.
10°F

Temperature rise the CG pumps assumeBuilt-in pump flow is set for this rise at full load. A mold or plate exchanger that needs a 4°F rise wants a separate circulation loop, not a bigger compressor.

Before you order

Where It Will Stand

1.

Air


Air-cooled units need the room to stay under 95°F with the chiller running.

Allow for the load plus the compressor heat.

2.

Water


Water-cooled units need 60°F city water or 85°F tower water.

And a drain or a return for it.

3.

Power


A three-phase feed at 230V, 460V or 575V.

Check the voltages the model you pick is built for.

CG PORTABLES UNDER 5 TONS

Part Number Series Tons (50°F) Condenser Process Flow Reservoir Voltage Shipping Weight
CG-2A CG Air-Cooled 2 Air-Cooled 4.8 GPM 7.5 gal 230V / 460V 415 lbs
CG-3A CG Air-Cooled 2.9 Air-Cooled 7.2 GPM 7.5 gal 230V / 460V 600 lbs
CG-4A CG Air-Cooled 4 Air-Cooled 9.6 GPM 25 gal 230V / 460V / 575V 800 lbs
CGD-5A CG Air-Cooled 4.9 Air-Cooled 12 GPM 25 gal 230V / 460V / 575V 800 lbs
CG-2W CG Water-Cooled 2 Water-Cooled 4.8 GPM 7.5 gal 230V / 460V / 575V 445 lbs
CG-3W CG Water-Cooled 3 Water-Cooled 7.2 GPM 7.5 gal 230V / 460V / 575V 470 lbs

Ratings at 50°F leaving water; air-cooled ratings at 95°F ambient. Flow is the built-in process pump's published flow.

Matching a CG Portable to the Duty

Six CG portables from 2 to 4.9 tons for machine tools, molding presses, jacketed vessels and small cellars on three-phase power.

Machine-tool coolant, a single injection press, a jacketed reactor, a small cellar of fermenters: most three-phase portable duties in this range are one load at one setpoint. The selection is the capacity at that setpoint, the flow the load needs, and where the heat goes.

Flow and temperature rise

The pumps are sized for about a 10°F rise at full load - 4.8 GPM on the 2-ton units, 12 GPM on the CGD-5A. A mold or a plate exchanger that needs a 4°F rise at 4 tons needs 24 GPM, more than twice what the CG-4A pump moves. That duty wants a separate circulation loop or a larger unit's pump, not the next compressor size.

Water-cooled in a hot room

Where a portable would sit in a 100°F press hall or a mechanical room with no ventilation, the water-cooled units keep their rating whatever the room temperature, provided the water supply is there. They are also lighter than the air-cooled units of the same size: 470 lbs shipping for the CG-3W against 600 lbs for the CG-3A.

Past 5 tons

The CG range continues to 29 tons air-cooled and 40 tons water-cooled on the Indoor Packaged Units page of the 5 to 40 ton range.

The other line we supply covers this range as well - see its 2 to 15 ton portable chillers on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

What Engineers Ask About 2 to 4.9 Ton CG Portables

About 0.9 ton of rating and 2.4 GPM of pump: the CGD-5A carries 4.9 tons of rating and a 12 GPM pump, the CG-4A 4 tons with 9.6 GPM. Both carry 25-gallon tanks, ship at 800 lbs and are offered at 230V, 460V and 575V. At 460V the CGD-5A is a 17-amp load and the CG-4A a 12-amp one, so a feeder sized for one is not automatically right for the other. With tank and weight the same, choose on the load at your setpoint, and take the CGD-5A when the 4-ton unit would run flat out.

The 2-ton units: the CG-2A ships at 415 lbs and the CG-2W at 445, about half the 800 lbs of the CG-4A and CGD-5A. Weight climbs faster on the air-cooled side, from 415 lbs at 2 tons to 600 at 2.9, while the water-cooled CG-3W is only 470 at 3 tons. That makes the CG-3W the lightest unit per ton here, though it needs a water supply and a drain at every new location, which often matters more than the weight. For a unit that moves between machines every week, the air-cooled CG-2A or CG-3A needs only power and process connections.

We don't quote these units on phase converters. Where a site has only single-phase power, the answer is the CF single-phase line up to 1.5 tons, or a pair of CF units, each on its own circuit, for a larger load that can be split. If three-phase service is available, check its voltage against the model too, since the 2- and 3-ton air-cooled units are built only for 230V or 460V. A converter also adds a failure point between the utility and the compressor, and a stopped converter stops the process as surely as a failed chiller.

Close, but not quite: the CG-3A is rated 2.9 tons and the CGD-5A 4.9, both at 50°F leaving water and 95°F ambient. A load measured at exactly 3 tons does not fit the CG-3A; it goes to the water-cooled CG-3W at 3 tons or up to the CG-4A. A true 5-ton load is past this page entirely, into the CG range on the 5 to 40 ton pages. Then apply the setpoint: these ratings fall below 50°F, so a duty held at a glycol setpoint needs the next size up more often than the names suggest.

It works on paper, but it is rarely the best answer for the duty. A 2-ton load that must hold a 4°F rise needs 12 GPM, exactly the CGD-5A's pump, so the 4.9-ton unit would meet the flow. It would also run its compressor at well under half load, cycle more, and cost more to buy and power than the duty justifies. A CG-2A or CG-2W feeding a small tank, with a separate circulation pump sized for 12 GPM to the load, holds the rise with a chiller matched to the heat. Pick the larger unit only when the load is expected to grow into it.