Heat rejected outdoors: TTOACS on a pad or condensers outside

Request a Quote

Two Ways to Reject Heat Outdoors

TTOACS, TTI Air-Cooled and MA Modules, 42.7 to 90 Tons

A plant without cooling-tower water still has to put 40 to 100 tons of heat somewhere, and outdoors is the only practical place. This page covers the two ways to do it: move the whole chiller outside, or keep the chiller inside and move only its condenser.

The TTOACS outdoor packages (42.7 to 84.6 tons here) carry condenser, compressors, tank and pumps on one frame and are published at 460V. The TTI air-cooled central chillers (50 to 90 tons) and MA chilling modules (46.4 to 90 tons) stay indoors and connect to a remote air-cooled condenser through refrigerant lines; they are published at 230V, 460V and 575V.

Air-cooled central glycol chiller, representative unit

WHAT TO SPECIFY

  • Outdoor package: the whole plant on a pad; the supply and return lines are its only connection to the building.
  • Designed to run in ambient air from -20°F to 95°F.
  • Remote condenser: compressors, tank and controls stay in a heated room; the condenser goes on the roof or a pad.
  • The refrigerant line set is installed in the field and the system charged on site.
  • Tank and pump: 150 to 400 gallons on the TTOACS units, 340 to 1,200 gallons on the TTI; MA modules use the plant's own.
  • Zones: one or two on the TTOACS, two or three on the TTI, one to three circuits on the MA modules.
-20°F

Low ambient limit of a TTOACS packageAn outdoor package runs down to this, but its compressors and controls are serviced in that weather. A remote condenser keeps them in a heated room at the cost of a field line set.

Outdoor or remote

Three Questions

1.

Floor space?


None inside: an outdoor package takes none.

Room to spare: a TTI or MA keeps compressors in reach.

2.

How cold?


Outdoor packages run to -20°F ambient.

A remote condenser keeps the chiller itself indoors.

3.

A pump tank?


Already there: MA modules add to it.

Not yet: a TTI or TTOACS brings its own.

OUTDOOR AND REMOTE-CONDENSER SYSTEMS, 40 TO 100 TONS

Part Number Series Tons (50°F) Condenser Zones Tank / Pump Voltage
TTI-50A TTI Air-Cooled 50 Remote Air-Cooled 2 340 gal / 120 GPM 230V / 460V / 575V
TTI-60A TTI Air-Cooled 57 Remote Air-Cooled 2 340 gal / 144 GPM 230V / 460V / 575V
TTI-80A TTI Air-Cooled 80 Remote Air-Cooled 2 1,200 gal / 240 GPM 230V / 460V / 575V
TTI-90A TTI Air-Cooled 85.5 Remote Air-Cooled 3 1,200 gal / 270 GPM 230V / 460V / 575V
TTI-100A TTI Air-Cooled 90 Remote Air-Cooled 2 1,200 gal / 300 GPM 230V / 460V / 575V
MA-50-RC-C MA Modules 46.4 Remote Air-Cooled 1 Separate 230V / 460V / 575V
MA-50-RC-CC MA Modules 50 Remote Air-Cooled 2 Separate 230V / 460V / 575V
MA-60-RC-C MA Modules 60 Remote Air-Cooled 1 Separate 230V / 460V / 575V
MA-60-RC-CC MA Modules 60 Remote Air-Cooled 2 Separate 230V / 460V / 575V
MA-70-RC-CC MA Modules 70 Remote Air-Cooled 2 Separate 230V / 460V / 575V
MA-80-RC-CC MA Modules 80 Remote Air-Cooled 2 Separate 230V / 460V / 575V
MA-100-RC-CC MA Modules 90 Remote Air-Cooled 2 Separate 230V / 460V / 575V
MA-90-RC-CCC MA Modules 90 Remote Air-Cooled 3 Separate 230V / 460V / 575V
TTOACS-50S-CG-1P TTOACS 42.7 Air-Cooled 1 150 gal / 120 GPM 460V
TTOACS-50D-MZC-2P TTOACS 48.4 Air-Cooled 2 200 gal / 120 GPM 460V
TTOACS-60S-CG-1P TTOACS 55.1 Air-Cooled 1 300 gal / 144 GPM 460V
TTOACS-60D-MZC-2P TTOACS 57.4 Air-Cooled 2 400 gal / 144 GPM 460V
TTOACS-80D-MZC-2P TTOACS 75.8 Air-Cooled 2 400 gal / 192 GPM 460V
TTOACS-100D-MZC-2P TTOACS 84.6 Air-Cooled 2 400 gal / 240 GPM 460V

Ratings at 50°F leaving water. TTI air-cooled and MA units are listed without their remote condensers; MA modules connect to a separate reservoir and pumping system.

Package or Remote Condenser

Heat rejected outdoors: complete TTOACS packages on a pad, or TTI chillers and MA modules indoors with their condensers outside.

The outdoor package is the simplest installation - a pad, power, and two insulated lines to the building - and the right answer where mechanical-room space is short. Its compressors and controls live outdoors, so service happens in the weather. The remote-condenser arrangement keeps them in a heated room, at the cost of a refrigerant line set that a refrigeration contractor installs and charges.

Model names and ratings

The model name is a size class, and in this range several ratings sit below it: the TTOACS-100D-MZC-2P is rated 84.6 tons, the TTI-100A 90 tons and the MA-100-RC-CC 90 tons at 50°F. Always select from the rated figure.

Glycol in the outdoor case

An outdoor package's own piping and tank sit in winter air, so its loop runs glycol at every setpoint. A remote-condenser system keeps the process loop indoors; only the refrigerant side goes outside, and the loop needs glycol only where the process setpoint or the building's own piping calls for it.

The other line we supply covers this range as well - see its outdoor air-cooled central chillers, 5 to 210 tons on our sister chiller site.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Outdoor Package or Remote Condenser: Site Questions

The TTI-80A and the MA-80-RC-CC, both rated 80 tons; the TTOACS-80D-MZC-2P is rated 75.8 and falls about 4 tons short. On the outdoor package route an 80-ton load moves up to the TTOACS-100D-MZC-2P at 84.6 tons, which leaves a modest margin. Between the other two, the difference is the tank: the TTI-80A carries 1,200 gallons and a 240 GPM pump, while the MA module relies on the plant's own reservoir and pumps.

More rating and more tank as well as the second zone, so the comparison is about more than redundancy. At the 50 size the TTOACS-50D-MZC-2P rates 48.4 tons with a 200-gallon tank, against 42.7 tons and 150 gallons for the single-zone TTOACS-50S-CG-1P; both run a 120 GPM pump. At the 60 size the gap narrows to 57.4 tons against 55.1, but the tank still grows from 300 to 400 gallons. For a 45-ton duty that means only the D model covers it at the 50 size, and a fault in one zone still leaves the loop roughly 24 tons.

Nearly equal on rating, 84.6 tons for the outdoor package and 85.5 for the TTI, but the TTI-90A keeps more running through a fault and carries three times the tank. Its three zones mean one zone down leaves about 57 tons, where the two zones of the TTOACS-100D-MZC-2P leave about 42. The TTI's 1,200 gallons against the package's 400 also count on a batch loop. In return the TTOACS needs no mechanical room, no line set and no field charge, and arrives ready for a pad. Voltage can decide it before any of that: the TTOACS is published at 460V only, the TTI at 230V, 460V and 575V.

Usually, for a plant that values running through a fault: both are rated 90 tons, but the three-circuit module loses about a third with one circuit down rather than half. That works out to roughly 60 tons left against 45. Three circuits also give finer steps, about 30 tons each against about 45, which helps a pump station whose load drifts through the day. Watch the name on the two-circuit module: it reads 100, the rating is 90, and a plan built from the name counts 10 tons that aren't there.

For a TTOACS package, two insulated process lines and a power feed, work a pipefitter and an electrician cover; for a TTI air-cooled chiller or MA module, refrigerant piping to the condenser, which is refrigeration-contractor work. The difference shows up in the schedule. Process piping can be run and pressure-tested before the chiller arrives. A remote-condenser job can't be finished until the chiller and condenser are both set, the lines are brazed, evacuated and charged, and the charge is checked under load. Put the refrigeration contractor in the installation quote from the start; a mechanical bid that leaves that scope out is a gap that tends to surface late.