100 to 210 Ton Glycol Chillers

Large central systems for bottling halls, breweries and dairies

Request a Quote

The Largest Single Units We List

Large central systems for bottling halls, production breweries, dairies and plant-wide process loops.

Above 100 tons a glycol chiller is plant infrastructure on the scale of the boiler or the air compressors, and it is planned the same way: around redundancy, the water or air available for heat rejection, and what the plant does when a unit is down. This range holds the largest single units in the line we supply.

Twenty-four Temptek units are rated above 100 and up to 210 tons at 50°F: ten TTI central chillers, ten MA and MW modules and four dual-zone TTOACS outdoor packages. The largest are 180 tons indoors - the TTI-180A, TTI-180W, MA-180-RC-CCC and MW-180-CCC - and 188 tons outdoors, the TTOACS-210D-MZC-2P.

Redundancy Is the Real Specification

At this size the question a plant manager asks is not whether the chiller is big enough but what happens when part of it stops. Almost every unit in this range carries two or three refrigeration zones or circuits. A three-zone 150-ton unit that loses a zone still delivers about two thirds of its capacity; a single-circuit unit that trips delivers none.

The second question is heat rejection. Indoors, the TTI water-cooled units and MW modules in this range need about 315 to 534 GPM of 85°F tower water at full load. Outdoors, the TTOACS packages and the remote-condenser TTI and MA systems put the heat into the air instead.

In This Range

Water-cooled chilling module, representative unit

Indoor Central Plant Systems:

Tower-Water Plants, 103 to 180 Tons

  • 11 part numbers
  • TTI and MW
  • Two or three zones
Air-cooled chilling module for a remote condenser, representative unit

Outdoor Central & Remote Condenser Systems:

Air-Rejected Plants, 103 to 188 Tons

  • 13 part numbers
  • TTOACS, TTI and MA
  • Heat rejected to air

SERIES FROM 100 TO 210 TONS

SERIES FORMAT CONDENSER TANK & PUMP MODELS RATED TONS (50°F)
TTI Air-Cooled Central, remote condenser Remote Air-Cooled Included 4 120 - 180
TTI Water-Cooled Central Water-Cooled Included 6 120 - 180
MA Modules Chilling module Remote Air-Cooled Separate 5 103 - 180
MW Modules Chilling module Water-Cooled Separate 5 103 - 180
TTOACS Outdoor package Air-Cooled Included 4 110.1 - 188
188 tons
largest single unit, rated at 50°F
270 tons
rating a 150-ton load needs at 28°F glycol
315 to 534 GPM
tower water for the indoor units, full load
900-gallon
tank on the largest outdoor package

Planning a 100 to 210 Ton Plant

Start with the plant's peak load at the coldest supply any process needs. At 28°F glycol a 150-ton plant load needs about 270 tons of 50°F rating - more than any single unit here, and the reason large glycol plants are usually two or three units on a common header.

A Model Name Is Not a Rating

Several model names in this range run ahead of their ratings. The TTOACS-210D-MZC-2P is rated 188 tons, the TTOACS-190D-MZC-2P 170.1 tons, and the MA-150-RC-CCC and MW-150-CCC 135 tons at 50°F. Every table in this section lists the rated figure; select from that, then apply the setpoint multiplier.

One large unit or two smaller ones

Two TTI-120W chillers give 255.6 tons of rating in two frames, each with its own tank and pump; one TTI-180W gives 180 tons in one. The pair takes more floor space and more piping. It also makes a plant that never loses all its cooling at once, and for a food or beverage plant where a stopped loop means lost product, the pair usualy wins.

Outdoor at this size

The dual-zone TTOACS packages from 110.1 to 188 tons carry 400- to 900-gallon tanks and 288 to 490 GPM pumps on one frame. They suit a plant with yard space and no tower, and they avoid a mechanical room entirely.

Call and talk it through with an engineer: 1-805-484-2992

Request a Quote

Planning Questions on 100 to 210 Ton Plants

About 105 tons, from the TTOACS-210D-MZC-2P and its 188-ton rating; the 180-ton indoor units come to roughly 100. That follows from this page's own ratio: a 150-ton load at 28°F calls for about 270 tons of 50°F rating, so divide any rating here by about 1.8 to see what it holds on a cold loop. The common mistake is reading the 50°F column, or the model name, as the answer. An MW-150-CCC bought for a 150-ton crash loop is rated 135 tons and carries about 75 at 28°F, half the load. Any cold-loop load above roughly 100 tons is a two-unit plant from the start.

The water-cooled TTI chillers and MW modules need a cooling tower with roughly 315 to 534 GPM of 85°F water to spare at full load; every other series sends its heat to outdoor air. The TTI air-cooled units and MA modules stay in the mechanical room and pipe refrigerant to condensers outside, so the site needs roof or pad space and a route for the refrigerant lines. The TTOACS packages need yard space and a pad, with only the header connection inside. Check the tower before choosing water: one already loaded by compressors or molding machines often has less spare flow than the plant assumes, and a unit starved of condenser water loses capacity on the days the process needs it most.

The MA and MW modules, which carry refrigeration only and connect to a separate tank and pump station; five of each are listed in this range, from 103 to 180 tons. A TTI or TTOACS brings its own tank and pump, duplicating equipment the plant already owns and adding a second reservoir to keep in balance. Before committing to modules, confirm two things: that the existing pumps can carry the extra flow a 103- to 180-ton module adds, and that the tank and header were sized for more than today's load. If either falls short, the job turns into a pump-station upgrade, and a complete TTI may cost less overall.

No figure is published for them yet; only the TTOACS-120D-MZC-2P carries a published 460V rating, so the electrical data for the three larger packages is settled when we prepare the quote. Put the plant's supply voltage in the request from the start. Meanwhile the indoor TTI chillers and the MA and MW modules here carry published ratings at 230V, 460V and 575V, all three-phase, which gives a 575V plant a known indoor or remote-condenser answer while the yard package is confirmed.

Not quite. The pair totals 255.6 tons of 50°F rating against the roughly 270 a 150-ton load needs at 28°F, which leaves the pair about 14 tons of rating, or roughly 8 tons of load, short at the coldest duty. A gap that small is easy to miss on a spreadsheet and large enough to show up as a supply temperature that creeps upward through every full production afternoon. Two 180-ton units, 360 tons combined, cover the load with margin. Three TTI-120W chillers, 383.4 tons, cover it as well, but with one of the three stopped they fall back to the same 255.6 and the same shortfall, so they are not a full-redundancy answer at this load.