Fractional-ton, air-cooled and single-phase: the chiller that sits beside one laser, one lab instrument or one small mold.

PRODUCT TYPE CAPACITY MODELS
Portable Chiller Air-Cooled ¼ to 1½ Tons 6

Specifications


Configuration & Size

Capacity:
0.29 to 1.5 tons
Models:
6 part numbers
Compressor:
Hermetic Reciprocating, Scroll
Process Flow:
0.7 to 3.6 GPM
Refrigerant:
R-513A

Construction

  • Stainless steel frame and enclosure
  • Brazed-plate evaporator, stainless plates
  • Brass positive-displacement pump
  • 4-gallon insulated reservoir
  • Casters and factory power cord

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • Glycol required below 48°F
  • Power: 115/1/60, 230/1/60
  • Design ambient 90°F, minimum 60°F

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

CF Series Fractional-Ton Portable Chillers

One Small Load, One Small Chiller

The CF is the smallest thing Temptek builds six models from 0.29 to 1.5 tons, every one air-cooled, every one on single-phase power. The whole circuit - a hermetic compressor, a brazed-plate evaporator, a 4-gallon tank and a brass positive-displacement pump - sits in a stainless cabinet about the size of a two-drawer file.

The pump is the detail that decides the application. A positive-displacement pump holds 60 PSI at a fraction of a gallon per minute, which suits a laser head, a spectrometer or a small hot-runner manifold with narrow passages. It does not suit a load that needs 10 GPM through a coarse jacket; that is a CG application.

Capacity is rated at 50°F leaving water with a 90°F design ambient. Below 48°F the fluid needs glycol, and the chiller delivers less than its nameplate the colder it runs.

The condenser heat stays in the room. A 1.5-ton CF rejects roughly 2 tons of heat through its own fan. In a small lab or enclosed cell that is the figure that decides whether it works.



injection molding machine with blue and red mold cooling lines

Small cabinet, single-phase cord, positive-displacement pump: built for one load at a steady flow.

Request a Quote

CF Series Applications

Laser cooling
Laser cooling
Lab and analytical instruments
Lab and analytical instruments
Small mold and hot runner
Small mold and hot runner
Bench-top process
Bench-top process

schematic of the CF Series air-cooled portable chillers circuit, showing where the process fluid and the condenser heat go

Heat In the Room, Flow at the Pump

Two numbers settle a CF selection, and neither is the tonnage. The first is where the condenser heat goes. The unit pulls room air across its condenser and puts the compressor work plus the process load back into the space, so a 1-ton CF in a closed 10 by 12 foot room will push that room past its 90°F design ambient within an afternoon, and the chiller then loses capacity exactly when it is needed. Temptek gives 60°F as the minimum ambient, so an unheated outbuilding is no better.

The second is the flow. The positive-displacement pumps run 0.7 to 3.6 GPM at 60 PSI. That is plenty of pressure for a small instrument circuit and nowhere near enough flow for a large one. If the process needs more than about 4 GPM, look at the CG range, which starts at 2 tons with a centrifugal pump.

Sizing, glycol mix and setpoint are covered in the glycol chiller sizing guide.
Call and talk it through with an engineer: 1-805-484-2992

Before You Order a CF Fractional-Ton Chiller

About 10°F at both ends of the range. On the water formula, the CF-1.5A's 1.5 tons, 18,000 Btu/h, over its 3.6 GPM is a 10°F rise, and the smallest model's 0.29 tons over 0.7 GPM comes out the same. That suits an instrument that tolerates a 10°F difference between supply and return. A laser head that wants a 2 or 3°F rise needs three to five times the flow, which the positive-displacement pump will not give; that load belongs on a CG with a centrifugal pump, or on a CF run well below its capacity.

Rarely. The CF-.33A is listed at 15 full-load amps on 115 V, which takes the whole of a 15-amp branch circuit, and most of a 20-amp one, before the instrument, a vacuum pump or a computer is plugged in beside it. Give the chiller its own circuit. The larger sizes ask more: the CF-1A and CF-1.5A are 230 V only, at 16.2 and 20 amps, and the other sizes can be ordered on either voltage. Check the receptacle type at the bench too, since each CF ships with a factory power cord for its voltage.

A fractional-ton portable from the M1 line, in the same format and capacity class, such as the M1-1A beside the CF-1A. We supply either. Send the load, the setpoint, the receptacle and the instrument's flow requirement, and we confirm which of the two suits it. In the same format, either one exhausts its condenser heat into the room it stands in, so the room check applies to both.

Yes, if the combined load fits the rating and the flow is split on purpose. A CF-1.5A's 3.6 GPM divided evenly gives each branch 1.8 GPM, enough on the water formula for about 9,000 Btu/h at a 10°F rise. A positive-displacement pump delivers a fixed total flow, and most of it goes to the less restrictive branch, so an instrument with fine passages beside an open jacket will be starved unless each branch has a balancing valve and a flow indicator. Both instruments also see the same supply temperature, so they must agree on the setpoint. Check the total too: a 0.5-ton spectrometer and a 1-ton laser together need the full 1.5 tons, and the 4-gallon reservoir gives almost no buffer when both start at once. The condenser heat of both loads, plus the compressor work, then goes into the room around the chiller.