| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Air-Cooled Scroll Chiller | Air-Cooled | 230 Tons nominal | R-454B |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ACS230 as shown on this page.
The Trane ACS230 is the 230-ton nominal size of the Ascend ACS air-cooled chiller, with 6 scroll compressors on two refrigerant circuits and 12 condenser fans. Trane lists an evaporator flow range of 276 to 828 GPM and capacity steps of 17-33-50-67-83-100 percent, on R-454B. The catalog gives the size as nominal tons; the rated capacity is on the nameplate and in Trane's selection data. Replacement: no single Temptek unit reaches 287.5 tons, so we supply it from our sister line: add-on chiller modules for plant-wide systems to 300 tons, paired to the load.
Specifications sourced from Trane's published product catalogs CG-PRC017AA-EN and AC-PRC002K-EN (tranetechnologies.com), October 2026. Trane, CGAM, Ascend and Symbio are trademarks of Trane Technologies; referenced here for cross-reference only. Sizes are Trane's nominal tons; rated performance comes from Trane's selection data. Confirm against the unit nameplate before ordering.