TTOACS Series

The whole chiller on a pad outside the wall: compressors, condenser, tank and pump, with only chilled fluid coming in.

PRODUCT TYPE CAPACITY MODELS
Outdoor Chiller Air-Cooled 5 to 188 Tons 21

Specifications


Configuration & Size

Capacity:
5.3 to 188 tons
Models:
21 part numbers
Compressor:
Digital Scroll, Rotary Screw, Scroll, Tandem Scroll
Process Flow:
12 to 490 GPM
Refrigerant:
R-454B, R-513A

Construction

  • Outdoor-rated packaged frame
  • Integral air-cooled condenser
  • Polyethylene or stainless reservoir
  • Brazed-plate or shell-and-tube evaporator
  • Optional standby process pump

Ratings

  • Rated at 50°F leaving fluid
  • 115°F condensing temperature
  • 0.80 / 0.60 / 0.40 at 40 / 30 / 20°F
  • Power: 460/3/60

Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.

TTOACS Outdoor Air-Cooled Central Chillers

A Packaged Plant That Lives Outdoors

The TTOACS puts everything outside. Compressors, air-cooled condenser, evaporator, reservoir and process pump sit in one outdoor-rated package, and only the chilled supply and return lines enter the building. Twenty-one models run from about 5 to 188 tons.

Single-zone S models run to 60 tons with the CG controller, a brazed-plate evaporator and 65 to 300-gallon reservoirs. Dual-zone D models run to the largest sizes with the multizone MZC controller, an evaporator pump and reservoirs of 150 to 900 gallons in polyethylene or stainless steel; the largest use rotary screw compressors and shell-and-tube evaporators.

A standby process pump is available on every size, which matters when the chiller is the only cooling the plant has.

Ratings are at 50°F leaving water and 115°F condensing, with 0.80, 0.60 and 0.40 multipliers at 40, 30 and 20°F.



laser cutting machine cutting sheet metal in a factory

Everything outdoors on one pad; the building sees only chilled glycol supply and return.

Request a Quote

TTOACS Series Applications

Outdoor pad installations
Outdoor pad installations
Glycol freeze protection
Glycol freeze protection
Standby pump redundancy
Standby pump redundancy
Plant-wide process cooling
Plant-wide process cooling

schematic of the TTOACS Series outdoor air-cooled central chillers circuit, showing where the process fluid and the condenser heat go

Winter Is the Design Condition Too

An outdoor chiller has to survive the coldest night of the year with the process shut down, not only the hottest afternoon at full load. The loop needs enough glycol to protect the reservoir, pumps and exposed piping at the lowest ambient the site sees, and the concentration chosen for freeze protection reduces capacity and raises pump head. That trade-off belongs in the selection, not the commissioning.

The published capacities also need a careful read. Several TTOACS part-number pages rate below the figure in the product menu - the TTOACS-50S-CG-1P at 42.7 tons, the TTOACS-100D-MZC-2P at 84.6 - and the two largest are listed under one model number and specified under another. We work from the unit page figures, and on a replacement we would rather see the load.

See glycol type and mix.
Call and talk it through with an engineer: 1-805-484-2992

TTOACS Outdoor Chillers: Questions Buyers Ask

Size, zone count, controller, pump count: TTOACS-60D-MZC-2P is the 60 size, dual-zone (D, where S means single), on the multizone MZC controller, with two pumps. The second pump is the evaporator pump the dual-zone units carry beside the process pump; the TTOACS-80D-MZC-2P, for example, pairs a 5 HP evaporator pump at 192 GPM with a 10 HP process pump. Single-zone units run one process pump with the CG controller. The size in the code is not the rating, so take the listed tons from the part-number page.

Yes, with room to spare. The unit is listed at 57.4 tons at 50°F and makes about 34.4 tons at 30°F on Temptek's 0.60 multiplier, or 413,000 Btu/h, and 144 GPM carries that at a rise near 5.7°F on the water formula. At the full 50°F rating the same flow gives about 9.6°F. A header designed for a wider rise on lower flow will see colder returns than expected, so the extra flow is no problem; a header that needs more than 144 GPM calls for a different pump. At 20°F the unit falls to about 23 tons.

The part-number page lists 260.8 system amps on 460 V three-phase, one figure for the whole package. That is about 3.1 amps per listed ton on its 84.6 tons. Smaller dual-zone units are listed at 59.2 amps for the TTOACS-20D-MZC-2P and 130.2 for the TTOACS-50D-MZC-2P. Every TTOACS is listed at 460 V and 60 Hz, so a plant on another voltage should say so with the inquiry, before the pad and the feeder are designed.

A pump failure. A dual-zone TTOACS keeps cooling if a compressor or circuit drops out, but the process flow still depends on one process pump, so a failed seal or motor stops glycol to the whole header while both refrigeration circuits sit idle. The standby pump, offered on every size, takes over that duty. On a single-zone S unit the process pump and the one refrigeration zone are each single points of failure, and the standby pump covers one of them. For a plant whose product spoils in hours, add it at order time; it is simpler to build in than to fit later on the pad.

Usually an outdoor air-cooled unit of the same format and capacity class, for example the OACS-30S-MG-1P beside the TTOACS-30S-CG-1P. Some pages name the next size up instead, as on the TTOACS-100D-MZC-2P, and there it pays to compare closely, since that unit is listed at 84.6 tons, well under it's model number. We supply either one. Compare the two on the listed tons at your setpoint, the pumps and the reservoir, rather than on the names.