Temptek
Product Type Capacity Refrigerant
Outdoor Chiller Outdoor 10.2 Tons R-454B

Note: Unit pictured is the alternate unit, representative of standard unit, and may not exactly depict p/n TTOACS-10S-CG-1P as shown on this page.

Chiller equivalent to Temptek TTOACS-10S-CG-1P

Description

The Temptek TTOACS-10S-CG-1P is a outdoor air-cooled central chiller rated 10.2 tons at 50°F leaving fluid and 115°F condensing temperature, on 1 refrigeration zone. It runs a digital scroll compressor on R-454B. The process pump delivers 24 GPM at 48 PSI (2 HP) from a 68 gal reservoir. At a glycol setpoint the published multipliers apply: about 8.16 tons at 40°F, 6.12 at 30°F and 4.08 at 20°F. Also available: the alternate OACS-10S-MG-1P, the same outdoor air-cooled format and capacity class.

Product Overview

Part Number:
TTOACS-10S-CG-1P
Manufacturer:
Temptek
Series:
TTOACS Series
Alternate Unit:
OACS-10S-MG-1P

Configuration & Specifications

Refrigeration Zones Quantity:
1
Capacity (Tons):
10.2
Capacity (kW):
35.7
Compressor Type:
Digital Scroll
Refrigerant Type:
R-454B
Condenser Quantity of Fans:
1
Evaporator Type:
Brazed Plate
Controller Type:
MG Series
Rating Basis:
50°F leaving fluid, 115°F condensing

Process Pump & Reservoir

  • Process Pump HP: 2
  • Process Pump GPM: 24
  • Process Pump PSI: 48
  • Standby Pump Offered: Optional
  • Reservoir: 68 gal
  • Reservoir Construction: Polyethylene

Electrical

  • Voltage: 460V
  • Phase: Three Phase
  • Frequency: 60 Hz
  • System Amps: 28.5

Connections, Dimensions & Weight

Connection Type:
NPT
Connection Size:
1-1/4"
Height:
87"
Width:
60"
Depth:
75"