The same press-side chiller with a water-cooled condenser: no hot air on the floor, and one more water system to size.
| PRODUCT | TYPE | CAPACITY | MODELS |
|---|---|---|---|
| Portable Chiller | Water-Cooled | 2 to 40 Tons | 10 |
Specifications are Temptek's published figures (September 2026); confirm against the unit nameplate before ordering.
Ten models run from 2 to 40 tons with the same tank, stainless or cast-iron centrifugal pump and control as the air-cooled CG, but a water-cooled condenser in place of the fan. The water-cooled line goes 10 tons further, to the CG-40W.
The condenser needs its own water supply. Temptek lists two figures for every size: city water at 60°F with a 20 PSI differential, and tower water at 85°F. Tower flow is about twice city flow - the CG-20W wants 32 GPM of city water or 63 GPM from a tower.
Ratings are at 50°F leaving water and 105°F condensing, ten degrees lower than the air-cooled units because the condenser sees cooler water than room air.
City water is a running cost. A once-through condenser on city water sends that flow to drain for every hour the chiller runs. Where a tower or a plant loop exists, it is the better source.
A water-cooled condenser in the portable cabinet, fed from a tower or plant water loop.
Request a Quote
A water-cooled portable is only as good as the water it gets. The condenser flows Temptek publishes assume a clean condenser, 85°F tower water and a 20 PSI differential across the unit. Feed it 90°F water in August, or let the tubes scale, and head pressure climbs until the unit trips on high pressure - usually on the hottest afternoon of the year.
On a replacement, measure what the old unit actually receives: supply temperature, flow and the pressure available at the connections. A tower loop that was sized for one CG-20W will not carry a second one added later. The condenser supply and drain connections are listed on each part-number page, and they are usually smaller than the process connections.
Condenser water planning is covered in condenser water and remote condenser planning.