The Carrier AquaSnap 30RC in two size ranges, 35 part numbers, from 10 to 252 nominal tons. Each one is listed with its product data and the unit we supply in its place.
The AquaSnap 30RC is Carrier's packaged air-cooled scroll chiller. Carrier publishes it in two product data books: sizes 010 to 060, with a brazed plate evaporator and an optional hydronic module with pumps on board, and sizes 067 to 252, in standard and compact tiers. Both run on R-32. Carrier builds it for comfort cooling, but it takes a glycol loop: below a 40°F set point an inhibited antifreeze is required, and the larger sizes are ordered as brine application chillers below 38°F. Thermal Care sells the Carrier 30RC scroll chiller, 60 to 250 tons, as its 30 Series, so a Thermal Care 30RC nameplate is looked up here.
30RC, then three digits. The digits are the size, close to nominal tons: a 30RC050 is the 50-ton size, a 30RC112 the 112-ton size.
The voltage digit follows. 1 is 575 V, 2 is 380 V, 5 is 208/230 V and 6 is 460 V, all three-phase 60 Hz.
On sizes 067 to 252, position 10 is the tier. S is standard and C is compact: the compact unit puts the same nominal size on a shorter frame, 105 inches against 152 on the 092, for example. Position 11 carries an H on a brine application chiller, one ordered for leaving temperatures below 38°F. That digit is the one to check on a process loop. The tonnage and capacity guide explains nominal against working capacity.
We do not sell Carrier equipment. We supply new Temptek process chillers, and every Carrier part-number page names the Temptek unit we would put in its place. Carrier sizes the 30RC at AHRI conditions, 44°F leaving water and 95°F ambient; Temptek rates at 50°F and 95°F. A chiller makes less at 44°F then at 50°F, so the Carrier tons are matched on Temptek's published 40°F multiplier of 0.80: the Carrier figure divided by 0.80, which leaves the pick some margin.
The Carrier figure here is the nominal size, so we confirm against the nameplate and your set point before quoting. From the 152-ton size up, the divided figure passes the largest single Temptek outdoor chiller, and those pages point to the add-on module range on our sister site. Send the full model number, the serial, the set point and the glycol mix.
Call and talk it through with an engineer: 1-805-484-2992
Specifications sourced from Carrier's published AquaSnap 30RC product data, Forms 30RC-100PD and 30RC-3PD (carrier.com), October 2026. Carrier and AquaSnap are trademarks of Carrier; referenced here for cross-reference only. Sizes are Carrier's nominal tons; ratings come from Carrier's selection program. Confirm against the unit nameplate before ordering.
Older units in the field may still run R-22 or R-410A. What the refrigerant change means for service, retrofit and replacement.
+ Learn More
Rigging, electrical, piping and start-up items to settle before the old chiller comes out of service.
+ Learn More
Short cycling, rising amps, a tank that will not pull down: the symptoms that say the old unit is near the end.
+ Learn More