AquaSnap 30RC 010-060 Series

Carrier's small air-cooled scroll chiller: the AquaSnap 30RC, 10 to 60 nominal tons on R-32, with pumps on board as an option.

PRODUCT TYPE CAPACITY MODELS
Air-Cooled Scroll Chiller Packaged, Air-Cooled 10 to 60 nominal tons 11

Specifications


Configuration & Size

Capacity:
10 to 60 nominal tons
Models:
11 part numbers
Refrigerant:
R-32
Circuits:
1 to size 030, 2 from 035
Weight:
937 to 2,646 lb operating

Construction

  • Hermetic scroll compressors
  • Brazed plate evaporator
  • Microchannel condenser coil
  • Optional hydronic module with pumps
  • Factory 20-mesh strainer and flow switch

Ratings

  • Nominal size, AHRI 550/590
  • Leaving water 38 to 70°F
  • Antifreeze below a 40°F set point
  • Runs to 120°F ambient

Specifications sourced from Carrier's published AquaSnap 30RC product data, Forms 30RC-100PD and 30RC-3PD (carrier.com), October 2026. Carrier and AquaSnap are trademarks of Carrier; referenced here for cross-reference only. Sizes are Carrier's nominal tons; ratings come from Carrier's selection program. Confirm against the unit nameplate before ordering.

AquaSnap 30RC, 10 to 60 Nominal Tons

Eleven Sizes, Pumps Optional

Eleven sizes. 010 to 030 with two scroll compressors on one circuit; 035 to 060 with four compressors on two circuits.

Compact footprints. 67 or 89 inches long; 40 inches wide to size 030 and 92 inches from 035, not counting the control panel overhang.

Hydronic module. An optional single or dual pump package with strainer, expansion tank, flow switch and balance valve mounts in the unit.

Light on charge. With the microchannel condenser the whole unit holds 7.5 to 28 lb of R-32.



rows of filled water bottles with blue caps on a bottling conveyor

Scroll compressors, a brazed plate evaporator and a microchannel condenser, with an optional hydronic module.

Request a Quote

AquaSnap 30RC 010-060 Series Applications

Chilled water
Chilled water
Brewery glycol
Brewery glycol
Plastics molding
Plastics molding
Outdoor pads
Outdoor pads

schematic of the AquaSnap 30RC 010-060 series circuit, showing where the process fluid and the condenser heat go

A 38°F Floor Without Antifreeze

Carrier lists a minimum leaving water temperature of 38°F for the standard unit and requires an inhibited antifreeze for any set point under 40°F. A cellar loop at 28°F is a different duty from the nominal tons, so the set point decides the replacement. The leaving fluid temperature guide shows how capacity falls with set point.

Every part-number page below names the Temptek unit we supply in its place, sized from Carrier's nominal tons on Temptek's 0.80 multiplier at 40°F, or points to the add-on module range where the size is past a single chiller.
Call and talk it through with an engineer: 1-805-484-2992

Carrier AquaSnap 30RC, 10 to 60 Tons: Buyer Questions

Pumping, expansion and balancing all go with it, because the pumps, expansion tank, flow switch, balance valve and strainer were built into the chiller. Decide where each function lives afterward, on the new unit or on a separate pump and tank station, before the old one is disconnected. Pressure is the other check. Carrier lists the water side at 300 psig without the pump and 150 psig with it, so a pumped 30RC loop was limited to 150 psig at the chiller. Note the pump's flow and head, and whether that internal expansion tank was the only one on the loop.

Because Carrier's two limits differ: 38°F is the lowest leaving water the standard unit allows, but anything under a 40°F set point requires an inhibited antifreeze solution. That leaves a 2°F band, 38 and 39°F, inside the operating range yet not permitted on plain water. The slip is easy to make, since 38 or 39°F looks legal against the operating range, and on plain water it is the brazed plate evaporator that pays for it. When a unit like that is replaced, tell us the real set point and whether the loop has glycol now, since the new unit is sized and protected for the fluid actually in it.

Yes: Thermal Care lists Carrier's 30RC scroll chiller from 60 to 250 tons under its 30 Series name, so the cross-referance runs through the Carrier size. Only the bottom of that range touches this group, which ends at the 60-ton 30RC060 with four compressors on two circuits; anything larger belongs with the 30RC 067 to 252 models. A 60-ton Thermal Care unit would follow the 30RC060 match, the Temptek TTOACS-80D-MZC-2P rated 75.8 tons at 50°F. Send the full nameplate either way, because the Carrier size printed there decides the match, not the brand on the front panel.

At a 40°F set point, about 87 percent: the TTOACS-15S-CG-1P is rated 14.4 tons at 50°F, which Temptek's 0.80 multiplier puts at roughly 11.5 tons at 40°F, against the 30RC010's 10 nominal tons at 44°F. That is more headroom than the top of this range gets. The 30RC060 is matched to the TTOACS-80D-MZC-2P at 75.8 tons, or about 60.6 tons at 40°F, barely over its 60 nominal tons. So the small end has room for a little load growth and the 60-ton end has almost none. If the plant has added load since a 30RC060 went in, say so before the selection is fixed, and expect a call for rating at the set point you run.

Between 937 and 2,646 lb operating, depending on size, with an R-32 charge of 7.5 to 28 lb. The operating figure includes the water inside, so a drained chiller rigs out a little lighter, and the jump from 40 to 92 inches wide at size 035 changes the rigging plan. The R-32 has to be recovered by a certified technician before the unit is disconnected, so book that as its own step on the swap schedule.