1-805-484-2992

Quotes - Sizing - Sales

30RC025

Carrier
Product Type Capacity Refrigerant
Air-Cooled Scroll Chiller Air-Cooled 25 Tons nominal R-32

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n 30RC025 as shown on this page.

Replacement chiller for the Carrier 30RC025

Description

The Carrier 30RC025 is the 25-ton nominal size of the AquaSnap 30RC air-cooled scroll chiller, with 2 hermetic scroll compressors on one refrigerant circuit and a brazed plate evaporator. It runs on R-32 with 2 condenser fans moving 19,400 cfm, and weighs 1,445 lb operating with the microchannel condenser and no pump. Carrier gives the size as nominal tons; the rated capacity is on the nameplate and in Carrier's selection program. Replacement: we supply the Temptek TTOACS-40S-CG-1P, an outdoor air-cooled packaged chiller rated 38.4 tons at 50°F, against the 25 tons Carrier publishes for this unit at its nominal size (AHRI conditions, 44°F leaving water). Temptek rates at 50°F, so the 44°F figure is matched on Temptek's published 40°F capacity multiplier of 0.80, which leaves the pick some margin; we confirm it at your set point.

Product Overview

Part Number:
30RC025
Manufacturer:
Carrier
Replacement Unit:
Temptek TTOACS-40S-CG-1P

Published Capacity

Nominal Size:
25 tons
Rating Basis:
AHRI 550/590; ratings from Carrier's Packaged Chiller Builder
Leaving Water:
38°F minimum standard, 70°F maximum
Below 40°F Set Point:
Inhibited antifreeze solution required
High Ambient:
Starts and runs to 120°F; reduced capacity to 125°F

Configuration & Specifications

Compressors:
2 hermetic scroll
Circuit A Capacity:
26 tons
Refrigerant Circuits:
1
Minimum Capacity Step (standard):
50 %
Refrigerant:
R-32
Refrigerant Charge (MCHX):
12.75 lb
Condenser Fans:
2 x 30 in
Total Airflow:
19,400 cfm
Condenser Coil:
Microchannel standard; round tube plate fin optional

Evaporator & Hydronic Module

Evaporator:
Brazed plate, direct expansion
Net Fluid Volume:
3.72 gallons
Max Water-Side Pressure:
300 psig without pump; 150 psig with pump
Optional Hydronic Module:
Single or dual pump, strainer, expansion tank

Electrical

Voltages Offered:
208/230, 380, 460 or 575 V / 3 phase / 60 Hz

Connections

Chilled Water Inlet and Outlet:
2 in Victaulic

Dimensions & Weight

Length:
89 in
Width (without control panel overhang):
40 in
Height:
78 in
Shipping Weight (MCHX, no pump):
1,400 lb
Operating Weight (MCHX, no pump):
1,445 lb

Specifications sourced from Carrier's published AquaSnap 30RC product data, Forms 30RC-100PD and 30RC-3PD (carrier.com), October 2026. Carrier and AquaSnap are trademarks of Carrier; referenced here for cross-reference only. Sizes are Carrier's nominal tons; ratings come from Carrier's selection program. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales