1-805-484-2992

Quotes - Sizing - Sales

WCWC-480-E

Cold Shot
Product Type Capacity Refrigerant
Portable Chiller Water-Cooled Portable 40 Tons @ 50°F R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n WCWC-480-E as shown on this page.

Replacement chiller for the Cold Shot WCWC-480-E

Description

The Cold Shot WCWC-480-E is a water-cooled portable chiller with its pump and tank on board, from the WCWC Portable Water-Cooled line. Cold Shot publishes it at 480,000 Btu/h, 40 tons, at 50°F leaving fluid. Its stainless centrifugal process pump is listed at 7-1/2 hp, 160 GPM at 30 PSI. Cold Shot lists it for 208-230 V three-phase or 460 V three-phase power, with 2 in MNPT process connections. Replacement: we supply the Temptek CG-40W, a water-cooled portable chiller rated 40 tons at 50°F, against the 40 tons Cold Shot publishes for this unit at 50°F leaving fluid. Both makers rate at 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
WCWC-480-E
Manufacturer:
Cold Shot
Replacement Unit:
Temptek CG-40W

Published Capacity

Cooling Capacity:
480,000 Btu/h (40 tons)
Rating Basis:
50°F leaving fluid

Configuration & Specifications

Compressor:
Scroll
Refrigerant:
R-410A
Condenser:
Water-Cooled
Style:
Portable
Pump and Tank:
Pump and tank on board
Controls:
PLC with self-diagnostics; WiFi / LAN / LTE for the Guardian app

Pump & Reservoir

  • Process Pump: 7-1/2 hp
  • Pump Flow: 160 GPM at 30 PSI

Electrical

  • Voltage Options: 208-230V three-phase / 460V three-phase
  • Frequency: 60 Hz

Connections

Process Connections:
2 in MNPT, inlet and outlet

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales