1-805-484-2992

Quotes - Sizing - Sales

WCWC-60-E-ST

Cold Shot
Product Type Capacity Refrigerant
Central Chiller Water-Cooled Stationary 5 Tons @ 50°F R-410A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n WCWC-60-E-ST as shown on this page.

Replacement chiller for the Cold Shot WCWC-60-E-ST

Description

The Cold Shot WCWC-60-E-ST is a water-cooled stationary chiller, refrigeration only, with no pump or tank, from the WCWC Stationary Water-Cooled line. Cold Shot publishes it at 60,000 Btu/h, 5 tons, at 50°F leaving fluid and 85°F condenser water. It has no pump on board, so it is piped to a separate pump and reservoir, with the pump interlocked so the chiller cannot cool without flow. Cold Shot lists it for 208-230 V single-phase, 208-230 V three-phase or 460 V three-phase power, with 1 in MNPT process connections. Replacement: we supply the Temptek MW-5-C, a water-cooled chilling module rated 5 tons at 50°F, against the 5 tons Cold Shot publishes for this unit at 50°F leaving fluid and 85°F condenser water. Both makers rate at 50°F leaving fluid, so the comparison is like for like. Like this unit, it is refrigeration only and works with a pump-tank station, so the existing pumps and reservoir stay in place.

Product Overview

Part Number:
WCWC-60-E-ST
Manufacturer:
Cold Shot
Replacement Unit:
Temptek MW-5-C

Published Capacity

Cooling Capacity:
60,000 Btu/h (5 tons)
Rating Basis:
50°F leaving fluid, 85°F condenser water

Configuration & Specifications

Compressor:
Scroll
Refrigerant:
R-410A
Condenser:
Water-Cooled
Style:
Stationary
Pump and Tank:
Refrigeration only, no pump or tank
Controls:
PLC with self-diagnostics; WiFi / LAN / LTE for the Guardian app

Electrical

Voltage Options:
208-230V single-phase / 208-230V three-phase / 460V three-phase
Frequency:
60 Hz

Connections

Process Connections:
1 in MNPT, inlet and outlet

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales