1-805-484-2992

Quotes - Sizing - Sales
Replacement unit for the Cold Shot WCWC Stationary Water-Cooled Series

WCWC Stationary Water-Cooled Series

Water-cooled refrigeration for a plant that already has its pumps and tank: Cold Shot's stationary WCWC units, 1.5 to 80 tons.

PRODUCT TYPE CAPACITY MODELS
Central Chiller Water-Cooled Stationary 1.5 to 80 Tons 15

Specifications


Configuration & Size

Capacity:
1.5 to 80 tons at 50°F
Models:
15 part numbers
Pump:
Not on board
Condenser:
Water-cooled
Refrigerant:
R-410A

Construction

  • Scroll compressors, R-410A
  • Water-cooled condenser
  • Liquid receiver, head pressure control
  • Bronze Y-strainer, 20 mesh
  • Separate pump and reservoir

Ratings

  • Rated at 50°F leaving fluid
  • 85°F condenser water
  • Refrigerant R-410A
  • Separate pump and tank required

Specifications sourced from Cold Shot Chillers' published Chiller Specifications page, per-size chiller pages and EZ Chiller page (waterchillers.com), September 2026. Cold Shot Chillers, EZ Chiller and Guardian are trademarks of their owner; referenced here for cross-reference only. Confirm against the unit nameplate before ordering.

WCWC Stationary Water-Cooled Chillers, 1.5 to 80 Tons

Refrigeration Only, on Tower Water

Fifteen models, all with the ST suffix. Like the air-cooled stationary units, these have no pump and no tank; the chiller is piped to a separate pump and reservoir, with its own controls and power connection.

Capacity is published at 50°F leaving fluid on 85°F condenser water from 18,000 Btu/h on the WCWC-18-E-ST. Most of the 25-ton and larger units are listed on Cold Shot's per-size pages, where they carry the air-cooled footnote; the 50°F leaving-fluid figure is shown for each, up to 960,000 Btu/h on the WCWC-960-GC-ST.

Refrigeration components are listed. Cold Shot lists scroll compressors, sight glass and moisture indicators, balanced-port expansion valves, a filter drier, pressure-actuated head pressure control and a liquid receiver on its water-cooled units.

Stationary water-cooled units go inside. Cold Shot describes its water-cooled chillers as typically installed indoors, close to the tower loop and the plant's pump-tank system.



CNC machine cutting metal with sparks in a dark factory

A water-cooled refrigeration circuit that plugs into the pumps and reservoir the plant already runs.

Request a Quote

WCWC Stationary Water-Cooled Series Applications

Tower-water plants
Tower-water plants
Existing pump-tank systems
Existing pump-tank systems
Central process loops
Central process loops
Water-to-water plants
Water-to-water plants

schematic of the WCWC Stationary Water-Cooled series circuit, showing where the process fluid and the condenser heat go

Matching the Plant Around It

A stationary water-cooled chiller is a component in a plant: the tower, the condenser water pump, the process reservoir and the process pumps are all outside it. Replacing one is easiest when the new unit fits the same connections and the same flows, so the first thing to collect is the existing process and condenser water flow rates, the connection sizes and the voltage.

It is also the moment to check the condenser water. Cold Shot points out that untreated tower water leaves mineral deposits that cut heat transfer; a scaled condenser on the old unit may be why it no longer holds the set point. The tonnage and capacity guide explains how to count the load it actually has to carry.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the published 50°F capacity: a Temptek CG water-cooled portable to 3 tons, and from 5 tons a Temptek MW water-cooled chilling module, which like the stationary units carries no tank and works with a pump-tank station.
Call and talk it through with an engineer: 1-805-484-2992

What to Collect on a WCWC Stationary Replacement

Some: about 15 percent, enough for a modest drop in set point but not for a load that has already outgrown the old unit. The Temptek MW-10-C is rated 11.5 tons at 50°F against the 10 tons, 120,000 Btu/h, of the WCWC-120-E-ST, both on the 50°F leaving-fluid basis. Below 5 tons the MW is not used; sizes from 1.5 to 3 tons go to a Temptek CG water-cooled portable, which carries its own pump and tank, and the plant pump serving those small units can usually come out of the loop.

Measure the process flow and the temperature rise across the chiller, then multiply 500 by the flow in GPM and by the rise in °F, which gives Btu/h on water; divide by 12,000 for tons. For example, 40 GPM returning 6°F warmer than it leaves is 120,000 Btu/h, exactly the 10-ton rating of a WCWC-120-E-ST. Take the reading on a hot, busy afternoon, when the load peaks and the tower runs warmest. If the result is well below the rating but the unit still loses set point, the problem sits on the refrigeration or condenser side, not in the load, and the replacement can be sized on the real figure rather than oversized. If the result is at or above the rating, the load has grown, and the new unit is sized to the measured number plus the growth you expect.

Whether the old circuit was short of charge or wet, either of which explains a lost set point without any growth in load. A sight glass full of bubbles at steady running points to low charge or a restriction, and a moisture indicator showing wet means water in the refrigerant, often after a leak repair. Neither condition carries over to a new unit, but both change the diagnosis: a plant that blames the chiller's size when the circuit was simply low on charge buys more tons than it needs. Cold Shot lists both on its water-cooled units, alongside the filter drier, so a quick look by your refrigeration contractor is cheap insurance.

Because the loop that fouled the old evaporator will foul the new one: that bronze strainer was there to catch scale and debris coming back from the plant's reservoir. Stationary units sit on pump-tank stations that may be older than the chiller, with open reservoirs and steel piping shedding rust. Leave the strainer in place, or fit one if the Temptek module's inlet lacks it, and clean it on a schedule. A blocked strainer looks like a chiller fault: the flow drops, the rise accross the evaporator widens and the low-pressure safety trips.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales