| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Split-System Chiller | Split System | 20.7 Tons @ 55°F | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ES250S as shown on this page.
The Drake ES250S is a 20 hp single-circuit scroll split-system air-cooled chiller, from the ES / EST Split-System Scroll line. Drake publishes a capacity table for it rather than a single rating: 20.7 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 11.4. The same column runs from 13.7 tons at 35°F to 24.6 tons at 65°F. Drake lists one ZR250KCE compressor of 20 hp. Replacement: we supply the Temptek CG-25A-RC, an indoor chiller with a remote air-cooled condenser rated 23.1 tons at 50°F, against the 20.7 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.