| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Split-System Chiller | Split System | 56.9 Tons @ 55°F | R407C |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ES540Q as shown on this page.
The Drake ES540Q is a 52 hp tandem-circuit tandem scroll split-system air-cooled chiller, from the ES / EST Split-System Scroll line. Drake publishes a capacity table for it rather than a single rating: 56.9 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 683. The same column runs from 24 tons at 20°F to 63.3 tons at 60°F. Drake lists four ZR160KCE compressors of 13 hp each. Replacement: we supply the Temptek MA-60-RC-C, an air-cooled chilling module with a remote condenser rated 60 tons at 50°F, against the 56.9 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It is refrigeration only with a remote condenser, and works with a pump-tank station.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.