1-805-484-2992

Quotes - Sizing - Sales

ES840Q

Drake
Product Type Capacity Refrigerant
Split-System Chiller Split System 87.9 Tons @ 55°F R407C

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n ES840Q as shown on this page.

Replacement chiller for the Drake ES840Q

Description

The Drake ES840Q is an 80 hp tandem-circuit tandem scroll split-system air-cooled chiller, from the ES / EST Split-System Scroll line. Drake publishes a capacity table for it rather than a single rating: 87.9 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 1055. The same column runs from 39.5 tons at 20°F to 97.4 tons at 60°F. Drake lists four ZR250KCE compressors of 20 hp each. Replacement: we supply the Temptek MA-100-RC-CC, an air-cooled chilling module with a remote condenser rated 90 tons at 50°F, against the 87.9 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It is refrigeration only with a remote condenser, and works with a pump-tank station.

Product Overview

Part Number:
ES840Q
Manufacturer:
Drake
Replacement Unit:
Temptek MA-100-RC-CC

Published Capacity

Cooling Capacity:
87.9 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 20°F Leaving Fluid:
39.5 tons
Capacity at 35°F Leaving Fluid:
56.8 tons
Capacity at 45°F Leaving Fluid:
71.1 tons
Capacity at 60°F Leaving Fluid:
97.4 tons
R407C Suction Range:
10°F to 55°F

Configuration & Specifications

Horsepower:
80 HP
Compressor:
Tandem Scroll
Compressor Model:
4 x ZR250KCE, 20 hp each
Circuits:
Tandem
Condenser:
Remote Air-Cooled (split system)
Refrigerant:
R407C

Electrical

Voltage Options:
208-230 V three-phase / 460 V three-phase / 575 V three-phase
Frequency:
60 Hz

Connections

Process Connections:
3 in F-NPT

Dimensions & Weight

Evaporator Section (L x W x H):
110 x 34 x 77 in max
Evaporator Section Weight:
3,000 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form: