Product Type Capacity Refrigerant
Split-System Chiller Split System 1.6 Tons @ 50°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n EST18S as shown on this page.

Replacement chiller for the Drake EST18S

Description

The Drake EST18S is a 2 hp single-circuit scroll split-system air-cooled chiller with a tank, from the ES / EST Split-System Scroll line. Drake publishes a capacity table for it rather than a single rating: 1.6 tons at 50°F leaving fluid and 95°F ambient on R407C, at an EER of 8. The same column runs from 1.3 tons at 40°F to 2.4 tons at 70°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists one ZB15KCE compressor of 2 hp. Its tank holds 30 gallons. Replacement: we supply the Temptek CGD-5A-RC, an indoor chiller with a remote air-cooled condenser rated 4.9 tons at 50°F, against the 1.6 tons Drake publishes for this unit at 50°F leaving fluid and 95°F ambient on R407C. Temptek rates at the same 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
EST18S
Manufacturer:
Drake
Replacement Unit:
Temptek CGD-5A-RC

Published Capacity

Cooling Capacity:
1.6 tons at 50°F leaving fluid
Rating Point Used:
50°F leaving fluid, 95°F ambient, R407C
Capacity at 40°F Leaving Fluid:
1.3 tons
Capacity at 60°F Leaving Fluid:
2 tons
Capacity at 70°F Leaving Fluid:
2.4 tons
R404A Low-Temperature Range:
0.7 tons at 5°F to 2.1 tons at 60°F
R407C Suction Range:
25°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
2 HP
Compressor:
Scroll
Compressor Model:
1 x ZB15KCE
Circuits:
Single
Condenser:
Remote Air-Cooled (split system)
Tank:
Integral tank
Refrigerant:
R407C or R404A
Condenser Section:
CS18S

Pump & Reservoir

  • Tank Capacity: 30 gallons

Electrical

  • Voltage Options: 208-230 V single-phase / 208-230 V three-phase / 460 V three-phase
  • Frequency: 60 Hz

Connections

Process Connections:
3/4 in F-NPT

Dimensions & Weight

Evaporator Section (L x W x H):
34 x 38 x 57 in
Evaporator Section Weight:
600 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.