| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Air-Cooled Packaged | 30.8 Tons @ 50°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC400D-S as shown on this page.
The Drake PAC400D-S is a 40 hp dual-circuit semi-hermetic packaged air-cooled chiller, from the PAC Semi-Hermetic line. Drake publishes a capacity table for it rather than a single rating: 30.8 tons at 50°F leaving fluid and 95°F ambient on R407C, at an EER of 11.6. The same column runs from 14.7 tons at 20°F to 38.2 tons at 60°F. It is offered on R407C for a 10°F to 50°F suction range and R404A for a -10°F to 45°F suction range. Replacement: we supply the Temptek TTI-40A, an air-cooled central chiller rated 40 tons at 50°F, against the 30.8 tons Drake publishes for this unit at 50°F leaving fluid and 95°F ambient on R407C. Temptek rates at the same 50°F leaving fluid, so the comparison is like for like.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.