Replacement unit for the Drake PAC Semi-Hermetic Series

PAC Semi-Hermetic Series

Semi-hermetic compressors in Drake's packaged air-cooled cabinet: 10 to 100 hp, single or dual circuit, down to low-temperature duty on R404A.

PRODUCT TYPE CAPACITY MODELS
Packaged Chiller Air-Cooled Packaged 10 to 100 HP 21

Specifications


Configuration & Size

Horsepower:
10 to 100 hp
Models:
21 part numbers
Capacity:
10.6 to 86.5 tons at 55°F
Circuits:
Single or dual
Refrigerant:
R407C, R404A

Construction

  • Semi-hermetic compressors
  • Single or dual circuit
  • Air-cooled condenser
  • Stainless brazed plate evaporator
  • NEMA 3R electrical

Ratings

  • Tables from 20 to 65°F leaving
  • 95°F ambient column used
  • R407C 10 to 55°F suction
  • R404A -10 to 45°F suction

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

PAC Semi-Hermetic Packaged Chillers, 10 to 100 HP

Built for Colder Duty

Twenty-one models, single or dual circuit. The single-circuit PAC100S-S to PAC500S-S and the dual-circuit PAC150D-S to PAC1000D-S carry semi-hermetic compressors in place of scrolls.

The suction range is wider. Drake lists 10 to 55°F suction on R407C and -10 to 45°F on R404A, and its tables start at 20°F leaving fluid rather than 35°F.

Capacity is tabulated from 20 to 65°F. The PAC100S-S sheet lists 5.5 tons at 20°F up to 12 tons at 65°F leaving fluid in a 95°F ambient on R407C, with no 50°F row; the 55°F figure is used for the replacement.

No tank on these units. The semi-hermetic packaged units are chiller and condenser only, piped to a separate tank and pump.



long industrial process pipe rack with insulated pipes

Semi-hermetic compressors for low-temperature glycol, in a packaged air-cooled cabinet.

Request a Quote

PAC Semi-Hermetic Series Applications

Low-temperature glycol
Low-temperature glycol
Cold storage
Cold storage
Meat and seafood
Meat and seafood
Chemical process
Chemical process

schematic of the PAC Semi-Hermetic series circuit, showing where the process fluid and the condenser heat go

Low Temperature Changes the Match

These units are chosen for glycol well below 40°F, and at those set points the capacity is a fraction of the warm-water figure. The PAC100S-S makes 12 tons at 65°F but 5.5 at 20°F. A replacement sized at 50°F covers the warm end only; for a process at 20°F the selection has to be made at 20°F, with the glycol mix, and it usually lands on a larger unit.

The glycol type and mix guide covers the glycol side, and the leaving fluid temperature guide the capacity side.

Every part-number page below names the Temptek unit we supply in its place, matched at 50°F leaving fluid and 95°F ambient, a Temptek CG portable or TTI central chiller. For low-temperature duty, call us with the set point.
Call and talk it through with an engineer: 1-805-484-2992

Selection Notes on Drake PAC Semi-Hermetic Units

Somewhere near 22 tons, judging by Drake's PAC1000D-S table, which drops from 86.5 tons at 55°F to 39.9 tons at 20°F. That is 46% retained, so a 10-ton load divided by 0.46 needs about 21.7 tons at the warm rating point. The common mistake is reading a nameplate tonnage as good at any set point; at 20°F the machine delivers less than half of it. The glycol mix moves the answer further, since a stronger mix carries less heat per gallon. Use this only as a sanity check on an existing unit. We select the Temptek unit at your actual set point and concentration, not from the warm-water cross-reference.

On the smaller sizes it does: the PAC150D-S and PAC200S-S, for example, are covered by the Temptek CG-20AF, an air-cooled portable rated 19.3 tons at 50°F that carries its own tank and pump. Every PAC -S is chiller and condenser only, so the plant already has a tank and pump that the new portable can replace or run beside. From the PAC301S-S up, the match is a TTI central chiller such as the TTI-40A, rated 40 tons, and the existing tank and pump arrangement is reviewed with that selection. Send their sizes with the model number.

About 208 GPM of water, assuming a 10°F evaporator rise and its 86.5-ton rating at 55°F: 86.5 x 12,000 is 1,038,000 BTU/hr, and dividing by 500 x 10 gives 207.6 GPM. A glycol mix needs more flow than water for the same heat, so the real figure is higher. The connections step with size, 2 inch F-NPT on the PAC150D-S, 3 inch on the PAC500S-S and 4 inch on the PAC1000D-S, and the header feeding them should be checked against the flow rather than judged from the pipe size. Send the flow and head of the pump now feeding the header, since it may stay in service.

It can, so state the voltage first. The sampled PAC -S sheets show three-phase at 208-230 V, 460 V or 575 V, and the Temptek unit is confirmed against your supply rather than copied from the Drake sheet. A voltage change midway through a quote reworks the feeder, the disconnect and the chiller. Read it at the disconnect, not from an old panel label.