| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Air-Cooled Packaged | 11.8 Tons @ 55°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC120D as shown on this page.
The Drake PAC120D is a 12 hp dual-circuit scroll packaged air-cooled chiller, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 11.8 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 11.7. The same column runs from 7.8 tons at 35°F to 14.2 tons at 65°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists two ZB45KCE compressors of 6 hp each. Replacement: we supply the Temptek CG-15AF, an air-cooled portable chiller rated 14.5 tons at 50°F, against the 11.8 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It carries its own tank and pump, which this Drake model does not.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.