Replacement unit for the Drake PAC / PACT Scroll Series

PAC / PACT Scroll Series

Drake's core line: Copeland scroll packaged air-cooled chillers from 1.5 to 120 hp, PAC without a tank and PACT with one.

PRODUCT TYPE CAPACITY MODELS
Packaged Chiller Air-Cooled Packaged 1.5 to 120 HP 84

Specifications


Configuration & Size

Horsepower:
1.5 to 120 hp
Models:
84 part numbers
Capacity:
1.3 to 133 tons at 50-55°F
Circuits:
Single, dual, multi, tandem
Refrigerant:
R407C, R404A

Construction

  • Copeland scroll, digital or tandem
  • Copper tube / aluminum fin condenser
  • Stainless brazed plate evaporator
  • Hot gas bypass, suction accumulator
  • NEMA 3R, indoor or outdoor

Ratings

  • Tables from 35 to 70°F leaving
  • 70 to 105°F ambient columns
  • R407C or R404A
  • MCS controller, BMS ready

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

PAC and PACT Scroll Packaged Chillers, 1.5 to 120 HP

Scroll, Digital Scroll and Tandem

Eighty-four models across six product lines. Single-circuit scroll units run 1.5 to 30 hp, single-circuit digital scroll 4 to 10 hp, dual-circuit scroll and digital scroll 8 to 60 hp, multi-circuit scroll 15 to 25 hp, and tandem-circuit scroll units 28 to 120 hp.

PACT means a tank. Thirty of the models are PACT units with an integral storage tank and recirculation pump, 30 to 135 gallons on the sizes that list one; the PAC units are refrigeration and condenser only, piped to your own tank and pump.

Capacity is a table, not a number. The PACT96D sheet lists 6.9 tons at 40°F, 8.5 tons at 50°F and 12.5 tons at 70°F leaving fluid in a 95°F ambient on R407C, and 3.5 to 10.7 tons on R404A from 5 to 60°F.

Digital scroll and tandem add control. Drake's digital scroll units modulate down to 40% of capacity, and its tandem units step from 25 to 100%, which matters on a load that swings through the day.



cold storage warehouse racking

Copeland scroll compressors, a copper-aluminum condenser and an MCS controller, rated for indoor or outdoor use.

Request a Quote

PAC / PACT Scroll Series Applications

Brewery glycol
Brewery glycol
Dairy and food
Dairy and food
Plastics molding
Plastics molding
Medical imaging
Medical imaging

schematic of the PAC / PACT Scroll series circuit, showing where the process fluid and the condenser heat go

PAC or PACT Decides the Piping

The first thing to establish on a Drake replacement is whether the old unit carries a tank. A PACT unit is the whole system; a PAC unit is piped to a tank and pump elsewhere in the plant, and that tank may stay. Temptek's portables carry their own tank and pump, which suits a PACT swap directly and, on a PAC swap, either replaces the separate tank or works alongside it.

The second is the set point. Drake's tables show how steeply capacity falls: a unit that makes 8.5 tons at 50°F makes about 7 at 40°F. The leaving fluid temperature guide explains the effect.

Every part-number page below names the Temptek unit we supply in its place, matched at 50°F leaving fluid and 95°F ambient: a Temptek CG air-cooled portable to 29 tons, and a TTI air-cooled central chiller above.
Call and talk it through with an engineer: 1-805-484-2992

PAC or PACT: Questions on Drake Scroll Packages

The two pumps end up fighting each other: each tries to set the flow, and the usual result is one pump deadheading or the portable's reservoir draining or overflowing. A PAC unit is refrigeration and condenser only, so the plant's pump and tank were the whole hydronic side. When a Temptek CG portable goes in with its own tank and pump, either the old tank becomes a buffer on a separate loop the portable draws from, or the old pump comes out. Tell us the existing pump's flow and head and the tank volume, and we lay out which arrangement suits the loop. A PACT swap avoids the question, since both machines are complete systems.

It marks a Copeland digital scroll, which Drake describes as modulating down to 40% of capacity, so a unit making 10 tons can follow the load smoothly down to about 4 tons before it has to cycle. Drake builds digital scroll units at 4 to 10 hp single-circuit and 8 to 60 hp dual-circuit. Its tandem units behave differently, stepping between 25 and 100%, a lower floor reached in steps rather than smoothly. On a brewery loop that swings from crash cooling to idle overnight, the diffrence shows up in how tightly the glycol holds set point. Tell us which suffix your unit carries so the replacement's control suits the load profile.

Because its published 41.3 tons at 55°F is well past the 29-ton CG-30A, the largest Temptek air-cooled portable. The TTI-50A, rated 50 tons at 50°F, leaves 8.7 tons of headroom. Smaller sizes stay portable, the 20.6-ton PAC180D taking the CG-25A at 24.5 tons. A central chiller changes the installation, so send the floor space and the route in, along with the existing tank and pump.

About 0.16 tons per degree between 50 and 40°F, close to 2% of its 50°F rating for every degree colder. Drake's sheet gives the PACT96D 6.9 tons at 40°F against 8.5 at 50°F, with 95°F air on R407C, and the slope is steeper at the warm end, where it gains 4 tons between 50 and 70°F, about 0.2 tons per degree. The mistake this catches is sizing at 50°F and then running a 42°F set point to speed up a crash: that alone costs about 1.3 tons on this unit. Size from the row for your real set point, and treat the warm rows as headroom you will not have in production.

Yes, with the nameplate in hand: that model is documented as a 4-ton packaged air-cooled tank chiller on R-22, with dual compressors and two 0.75 HP recirculating pumps on 460V three-phase. We size a packaged glycol chiller on a current refrigerant to the same 4 tons, then check the duty, because a unit that old may have been moved to a colder set point or a bigger load than it was bought for. The two pumps matter as well: if one serves a second loop, the replacement has to account for it. If your nameplate shows a diffrent configuration, send the details before we quote.