1-805-484-2992

Quotes - Sizing - Sales

PAC150M

Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 16.1 Tons @ 55°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC150M as shown on this page.

Replacement chiller for the Drake PAC150M

Description

The Drake PAC150M is a 16.5 hp multi-circuit scroll packaged air-cooled chiller, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 16.1 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 10.8. The same column runs from 11 tons at 35°F to 19.1 tons at 65°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists three ZB42KCE compressors of 5.5 hp each. Replacement: we supply the Temptek CG-20AF, an air-cooled portable chiller rated 19.3 tons at 50°F, against the 16.1 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It carries its own tank and pump, which this Drake model does not.

Product Overview

Part Number:
PAC150M
Manufacturer:
Drake
Replacement Unit:
Temptek CG-20AF

Published Capacity

Cooling Capacity:
16.1 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 35°F Leaving Fluid:
11 tons
Capacity at 45°F Leaving Fluid:
13.4 tons
Capacity at 65°F Leaving Fluid:
19.1 tons
R404A Low-Temperature Range:
6.1 tons at 0°F to 17.4 tons at 55°F
R407C Suction Range:
25°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
16.5 HP
Compressor:
Scroll
Compressor Model:
3 x ZB42KCE, 5.5 hp each
Circuits:
Multi
Condenser:
Air-Cooled
Refrigerant:
R407C or R404A

Electrical

Voltage Options:
208-230 V single-phase
Frequency:
60 Hz

Connections

Process Connections:
1-1/2 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
145 x 44.5 x 57 in
Weight:
1,750 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales