Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 20.7 Tons @ 55°F R407C

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC250S as shown on this page.

Replacement chiller for the Drake PAC250S

Description

The Drake PAC250S is a 20 hp single-circuit scroll packaged air-cooled chiller, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 20.7 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 11.4. The same column runs from 13.7 tons at 35°F to 24.6 tons at 65°F. Drake lists one ZR250KCE compressor of 20 hp. Replacement: we supply the Temptek CG-25A, an air-cooled portable chiller rated 24.5 tons at 50°F, against the 20.7 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It carries its own tank and pump, which this Drake model does not.

Product Overview

Part Number:
PAC250S
Manufacturer:
Drake
Replacement Unit:
Temptek CG-25A

Published Capacity

Cooling Capacity:
20.7 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 35°F Leaving Fluid:
13.7 tons
Capacity at 45°F Leaving Fluid:
17 tons
Capacity at 65°F Leaving Fluid:
24.6 tons
R407C Suction Range:
25°F to 55°F

Configuration & Specifications

Horsepower:
20 HP
Compressor:
Scroll
Compressor Model:
1 x ZR250KCE
Circuits:
Single
Condenser:
Air-Cooled
Refrigerant:
R407C

Electrical

Voltage Options:
208-230 V three-phase / 460 V three-phase / 575 V three-phase
Frequency:
60 Hz

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.