1-805-484-2992

Quotes - Sizing - Sales

PAC490Q-Z

Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 52.1 Tons @ 55°F R407C

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PAC490Q-Z as shown on this page.

Replacement chiller for the Drake PAC490Q-Z

Description

The Drake PAC490Q-Z is a 44 hp tandem-circuit tandem scroll packaged air-cooled chiller, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 52.1 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 626. The same column runs from 22.5 tons at 20°F to 57.8 tons at 60°F. Drake lists four ZR144KCE compressors of 11 hp each. Replacement: we supply the Temptek TTI-60A, an air-cooled central chiller rated 57 tons at 50°F, against the 52.1 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F. It is a central chiller rather than a portable, because the largest Temptek air-cooled portable, the CG-30A (29 tons), falls short of this figure.

Product Overview

Part Number:
PAC490Q-Z
Manufacturer:
Drake
Replacement Unit:
Temptek TTI-60A

Published Capacity

Cooling Capacity:
52.1 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 20°F Leaving Fluid:
22.5 tons
Capacity at 35°F Leaving Fluid:
33.3 tons
Capacity at 45°F Leaving Fluid:
42 tons
Capacity at 60°F Leaving Fluid:
57.8 tons
R407C Suction Range:
10°F to 55°F

Configuration & Specifications

Horsepower:
44 HP
Compressor:
Tandem Scroll
Compressor Model:
4 x ZR144KCE, 11 hp each
Circuits:
Tandem
Condenser:
Air-Cooled
Refrigerant:
R407C

Electrical

Voltage Options:
208-230 V three-phase / 460 V three-phase / 575 V three-phase
Frequency:
60 Hz

Connections

Process Connections:
2-1/2 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
131 x 83 x 76 in
Weight:
3,100 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales