| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Air-Cooled Packaged | 6.6 Tons @ 50°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PACT70S as shown on this page.
The Drake PACT70S is an 8 hp single-circuit scroll packaged air-cooled chiller with a tank, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 6.6 tons at 50°F leaving fluid and 95°F ambient on R407C, at an EER of 9.9. The same column runs from 5.3 tons at 40°F to 9.8 tons at 70°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists one ZB58KCE compressor of 8 hp. Its tank holds 60 gallons. Replacement: we supply the Temptek CGD-7.5A, an air-cooled portable chiller rated 7.2 tons at 50°F, against the 6.6 tons Drake publishes for this unit at 50°F leaving fluid and 95°F ambient on R407C. Temptek rates at the same 50°F leaving fluid, so the comparison is like for like.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.