1-805-484-2992

Quotes - Sizing - Sales

PACT72D-ZD

Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 6.4 Tons @ 50°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PACT72D-ZD as shown on this page.

Replacement chiller for the Drake PACT72D-ZD

Description

The Drake PACT72D-ZD is an 8 hp dual-circuit digital scroll packaged air-cooled chiller with a tank, from the PAC / PACT Scroll line. Drake publishes a capacity table for it rather than a single rating: 6.4 tons at 50°F leaving fluid and 95°F ambient on R407C, at an EER of 9. The same column runs from 5.1 tons at 40°F to 9.6 tons at 70°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Its tank holds 60 gallons. Replacement: we supply the Temptek CGD-7.5A, an air-cooled portable chiller rated 7.2 tons at 50°F, against the 6.4 tons Drake publishes for this unit at 50°F leaving fluid and 95°F ambient on R407C. Temptek rates at the same 50°F leaving fluid, so the comparison is like for like.

Product Overview

Part Number:
PACT72D-ZD
Manufacturer:
Drake
Replacement Unit:
Temptek CGD-7.5A

Published Capacity

Cooling Capacity:
6.4 tons at 50°F leaving fluid
Rating Point Used:
50°F leaving fluid, 95°F ambient, R407C
Capacity at 40°F Leaving Fluid:
5.1 tons
Capacity at 60°F Leaving Fluid:
7.9 tons
Capacity at 70°F Leaving Fluid:
9.6 tons
R404A Low-Temperature Range:
2.7 tons at 5°F to 8.2 tons at 60°F
R407C Suction Range:
25°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
8 HP
Compressor:
Digital Scroll
Circuits:
Dual
Condenser:
Air-Cooled
Tank:
Integral tank
Refrigerant:
R407C or R404A

Pump & Reservoir

  • Tank Capacity: 60 gallons

Electrical

  • Voltage Options: 208-230 V three-phase / 460 V three-phase / 575 V three-phase
  • Frequency: 60 Hz

Connections

Process Connections:
1-1/4 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
75 x 34 x 78 1/4 in
Weight:
1,100 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales