| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Packaged Chiller | Water-Cooled Packaged | 5.6 Tons @ 50°F | R407C or R404A |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PWC60S-ZD as shown on this page.
The Drake PWC60S-ZD is a 6 hp single-circuit digital scroll packaged water-cooled chiller, from the PWC / PWCT Scroll line. Drake publishes a capacity table for it rather than a single rating: 5.6 tons at 50°F leaving fluid and 105°F condensing temperature on R407C, at an EER of 14.9. The same column runs from 4.1 tons at 35°F to 7.5 tons at 65°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Replacement: we supply the Temptek CG-7.5W, a water-cooled portable chiller rated 7.6 tons at 50°F, against the 5.6 tons Drake publishes for this unit at 50°F leaving fluid and 105°F condensing temperature on R407C. Drake rates this water-cooled table by condensing temperature rather than water temperature; the 105°F column is the usual condensing point on 85°F tower water, and we confirm it with your water temperature.
Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.