Replacement unit for the Drake PWC / PWCT Scroll Series

PWC / PWCT Scroll Series

Drake's water-cooled packaged chillers: Copeland scroll compressors from 1.5 to 120 hp on tower or plant water, PWCT with a tank.

PRODUCT TYPE CAPACITY MODELS
Packaged Chiller Water-Cooled Packaged 1.5 to 120 HP 79

Specifications


Configuration & Size

Horsepower:
1.5 to 120 hp
Models:
79 part numbers
Capacity:
1.5 to 142 tons at 50-55°F
Circuits:
Single, dual, tandem
Refrigerant:
R407C, R404A

Construction

  • Copeland scroll, digital or tandem
  • Coaxial or shell-and-tube condenser
  • Stainless brazed plate evaporator
  • Hot gas bypass
  • NEMA 3R electrical

Ratings

  • Tables from 35 to 65°F leaving
  • Condensing or entering water columns
  • R407C or R404A
  • MCS controller, BMS ready

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

PWC and PWCT Scroll Water-Cooled Chillers, 1.5 to 120 HP

Quiet, Indoors, on Condenser Water

Seventy-nine models across five product lines. Single-circuit scroll units run 1.5 to 30 hp, digital scroll 4 to 10 hp, dual-circuit scroll and digital scroll 8 to 60 hp, and tandem scroll 28 to 120 hp. Thirty are PWCT units with a tank.

The condenser depends on size. Drake uses a coaxial tube-in-tube condenser, which it describes as having superior anti-fouling characteristics, or a shell-and-tube condenser, depending on the model.

The tables are by condensing temperature on most models. The PWC96D sheet lists 9.7 tons at 50°F leaving fluid and 105°F condensing on R407C. The tandem sheets instead list entering condenser water from 75 to 95°F.

Water-cooled units live indoors. Drake notes that they are installed indoors and suit low-noise environments, and that they need a continual condenser water source.



insulated refrigeration pipes in a cold storage plant

A scroll compressor and a water-cooled condenser in one cabinet: no fans, no room heat.

Request a Quote

PWC / PWCT Scroll Series Applications

Tower-water plants
Tower-water plants
Brewery cellars
Brewery cellars
Winery tank cooling
Winery tank cooling
Dairy processing
Dairy processing

schematic of the PWC / PWCT Scroll series circuit, showing where the process fluid and the condenser heat go

Condensing Temperature Is Not Water Temperature

Most of Drake's water-cooled sheets tabulate capacity against condensing temperature, 70 to 120°F, rather than against the water entering the condenser. On 85°F tower water a condenser usually runs near 105°F, which is the column these pages use; city or well water runs cooler and makes more. The tandem sheets list entering condenser water directly, and the 85°F column is used there.

The condenser water flow is part of the selection, roughly 3 GPM per ton on tower water. The indoor vs outdoor installation guide compares water-cooled with air-cooled arrangements.

Every part-number page below names the Temptek unit we supply in its place, matched at 50°F leaving fluid: a Temptek CG water-cooled portable to 40 tons, and a TTI water-cooled central chiller above.
Call and talk it through with an engineer: 1-805-484-2992

Drake PWC and PWCT Scroll: Condenser Water Questions

It drops, because warmer tower water pushes condensing up from the 105°F column the match uses toward the 120°F column, the last Drake tabulates. A tower that drifts up on a humid afternoon, or has fouled fill, moves the unit into a column where it makes less. Read your unit's 120°F column to see the drop, and send the tower's worst summer supply temperature.

Because a water-cooled condenser has nowhere else to put its heat: when the water stops or slows, condensing pressure climbs quickly and the unit trips on high pressure. On tower water, budget about 3 GPM per ton whenever the compressor runs, so a 10-ton PWC100D needs about 30 GPM. The usual failures are a shared tower pump that cycles with another process, or a city-water valve closed for maintenance. If the source can be interrupted, tell us, since an interlock or an air-cooled arrangement may be the better plan.

Yes for steady duty: both take the Temptek CGD-10W, a water-cooled portable rated 10.6 tons at 50°F. The PWC100D is published at 10 tons at 50°F and 105°F condensing, a margin of only 0.6 tons; the PWCT96D at 9.7 tons at 55°F, read from that row because its table has no 50°F entry. A 6% margin is enough on a steady tower, but not if the loop also takes a crash or a warm-tank startup, so give us the peak load rather than the average. The CG water-cooled range runs to 40 tons; above that a TTI central chiller takes over, as it does for the PWC540Q-Z.

Quite a lot: a condenser that scaled or plugged on the old unit tells you the same water will do the same to the new one, whatever condenser it carries. Drake fits a coaxial tube-in-tube condenser on some models, which it credits with superior fouling resistance, and a shell-and-tube condenser on others. If a coaxial unit still lost capacity to fouling, the water treatment is the problem, not the hardware. Check the cleaning history and any high head pressure trips, and tell us which condenser type you have along with the water source. A replacement on untreated water starts losing capacity in its first season.