1-805-484-2992

Quotes - Sizing - Sales

VPACT7S

Drake
Product Type Capacity Refrigerant
Packaged Chiller Air-Cooled Packaged 8.1 Tons @ 55°F R407C or R404A

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n VPACT7S as shown on this page.

Replacement chiller for the Drake VPACT7S

Description

The Drake VPACT7S is an 8 hp single-circuit scroll packaged air-cooled chiller with a tank, from the Value Line line. Drake publishes a capacity table for it rather than a single rating: 8.1 tons at 55°F leaving fluid and 95°F ambient on R407C, at an EER of 11.8. The same column runs from 5.3 tons at 35°F to 9.8 tons at 65°F. It is offered on R407C for a 25°F to 55°F suction range and R404A for a -10°F to 45°F suction range. Drake lists one ZB58KCE compressor of 8 hp. Its tank holds 31 gallons. Replacement: we supply the Temptek CGD-10A, an air-cooled portable chiller rated 9.8 tons at 50°F, against the 8.1 tons Drake publishes for this unit at 55°F leaving fluid and 95°F ambient on R407C. Drake's table has no 50°F row for this unit, so its 55°F figure is used; a chiller makes at least as much at a warmer set point, so the pick keeps a margin at 50°F.

Product Overview

Part Number:
VPACT7S
Manufacturer:
Drake
Replacement Unit:
Temptek CGD-10A

Published Capacity

Cooling Capacity:
8.1 tons at 55°F leaving fluid
Rating Point Used:
55°F leaving fluid, 95°F ambient, R407C
Capacity at 35°F Leaving Fluid:
5.3 tons
Capacity at 45°F Leaving Fluid:
6.6 tons
Capacity at 65°F Leaving Fluid:
9.8 tons
R404A Low-Temperature Range:
2.6 tons at 0°F to 7.9 tons at 55°F
R407C Suction Range:
25°F to 55°F
R404A Suction Range:
-10°F to 45°F

Configuration & Specifications

Horsepower:
8 HP
Compressor:
Scroll
Compressor Model:
1 x ZB58KCE
Circuits:
Single
Condenser:
Air-Cooled
Tank:
Integral tank
Refrigerant:
R407C or R404A

Pump & Reservoir

  • Tank Capacity: 31 gallons

Electrical

  • Voltage Options: 208-230 V three-phase / 460 V three-phase / 575 V three-phase
  • Frequency: 60 Hz

Connections

Process Connections:
1-1/4 in F-NPT

Dimensions & Weight

Dimensions (L x W x H):
87 x 34 x 47.5 in
Weight:
700 lbs

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales