Replacement unit for the Drake Value Line Series

Value Line Series

Drake's simplest packaged chiller: one scroll compressor, a polyethylene tank and a stand-alone microprocessor controller, 1.5 to 10 hp.

PRODUCT TYPE CAPACITY MODELS
Packaged Chiller Air-Cooled Packaged 1.5 to 10 HP 9

Specifications


Configuration & Size

Horsepower:
1.5 to 10 hp
Models:
9 part numbers
Capacity:
2.4 to 10.5 tons, 55°F / 95°F
Tank:
On every model
Refrigerant:
R407C, R404A

Construction

  • Copeland scroll compressor
  • Polyethylene storage tank
  • Stainless brazed plate evaporator
  • Hot gas bypass
  • NEMA 3R electrical

Ratings

  • Tables from 35 to 65°F leaving
  • 80 to 105°F ambient columns
  • R407C or R404A
  • Stand-alone microprocessor

Specifications sourced from Drake Refrigeration's published product-line pages and per-model specification sheets (drakechillers.com), September 2026. Drake Refrigeration and the model names shown are trademarks of their owner; Copeland is a trademark of its owner; referenced here for cross-reference only. Drake marks its sheets for reference only. Confirm against the unit nameplate before ordering.

Value Line Packaged Air-Cooled Chillers, 1.5 to 10 HP

The Cost-Effective End of the Range

Nine models, all with a tank. The VPACT1S to VPACT10S are single-circuit packaged air-cooled chillers on a Copeland scroll compressor, with a polyethylene storage tank and a stainless recirculation pump.

The controller is simpler. Where the rest of Drake's range uses a Micro Control Systems controller with BMS communications, the Value Line has a stand-alone microprocessor control; BMS, BAS and remote monitoring are an option.

Capacity comes as a table. The VPACT2S sheet, for example, lists 1.5 tons at 35°F up to 2.9 tons at 65°F leaving fluid in a 95°F ambient on R407C, and 0.9 to 2.7 tons from 0 to 55°F on R404A.

Two sheets are missing. The VPACT1S link on Drake's site does not open, and the VPACT8S sheet carries no capacity table; those two pages name no replacement and send you to an application specialist.



stainless food processing line with tanks and conveyors in blue light

One scroll compressor, a poly tank and a pump in one cabinet, rated for indoor or outdoor use.

Request a Quote

Value Line Series Applications

Small brewery cellars
Small brewery cellars
Winery tank jackets
Winery tank jackets
Small dairy loads
Small dairy loads
Lasers and instruments
Lasers and instruments

schematic of the Value Line series circuit, showing where the process fluid and the condenser heat go

Read the Table at Your Set Point

A Value Line unit's capacity depends heavily on where it runs. The VPACT2S makes 2.4 tons at 55°F leaving fluid in a 95°F ambient but 1.5 tons at 35°F, so the same box is a 2.5-ton chiller for mold water and a 1.5-ton chiller for a fermentation crash. Read the row for the set point you actually run, at your summer ambient.

The leaving fluid temperature guide explains why capacity falls with set point, and the glycol chiller sizing guide works the load itself.

Every part-number page below names the Temptek unit we supply in it's place, an air-cooled portable with its own tank, matched at 50°F leaving fluid and 95°F ambient.
Call and talk it through with an engineer: 1-805-484-2992

Drake Value Line in Practice: Small Tank Chillers

Every Value Line model carries a polyethylene tank and a stainless pump, sized 13 gallons on the VPACT2S and VPACT3S, 24 on the VPACT5S and VPACT6S, and 31 on the VPACT7S and VPACT10S. Those are small volumes, so the jackets and piping do much of the buffering. Tank volume smooths cycling; it adds no capacity. The Temptek portable named in its place has its own tank.

All of the process heat plus the compressor's own heat, since a packaged air-cooled unit rejects through its condenser into whatever space it occupies. At the top of the range, listed at 10.5 tons at 55°F, that is 126,000 BTU/hr of process heat before the compressor is counted; a VPACT2S at 2.4 tons adds 28,800 BTU/hr plus its motor. In a small cellar or a closed mechanical room, that heat raises the room temperature, the unit then works against a hotter ambient column, and capacity falls, a spiral that ends in high-pressure trips. Drake's tables run 80 to 105°F ambient, so read the column the room will actually reach.

About half a ton at the rating point. Drake lists the VPACT2S at 2.4 tons with 55°F leaving fluid, and the CG-3A is rated 2.9 tons at 50°F, covering it five degrees colder. That margin is for warm duty. If the VPACT2S was crash-cooling fermenters at 35°F, where it makes 1.5 tons, the comparison has to be made there. Tell us the set point the unit holds most of the day.

No: the sampled sheets list the VPACT6S and larger on three-phase only, 208-230, 460 or 575 V, while single-phase 208-230 V appears on the VPACT2S, VPACT3S and VPACT5S sheets. If a VPACT6S is running in a building with single-phase service, look at the disconnect, because it is either on a phase converter or the service is not what it seems. A single-phase supply narrows what we can supply at that size. Read the supply at the disconnect and include it with the model number.

Only if the old unit was ordered with Drake's BMS, BAS or remote monitoring option; the standard Value Line control is a stand-alone microprocessor with no network link to carry over. Check the controller for a communication card, or a cable run back to a building system, before assuming either way. If it reports to something, list what it sends, a high-temperature alarm or a run status for example, so the replacement can be wired to send the same signals. If it stands alone, the new unit simply takes its place on power and piping.