| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| One-Pass Chiller | Air-Cooled | 1.92 Tons @ 50°F | HFC |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PC-200-30 as shown on this page.
The Filtrine PC-200-30 is a 1.92-ton one-pass air-cooled chiller from the PC line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 23,000 Btu/h, 1.92 tons, at 50°F outlet and 90°F ambient, 13,500 Btu/h at 30°F and 30,000 Btu/h at 68°F, the point its model number is named for. As a one-pass chiller it has no pump: the liquid enters under its own pressure, passes through the tank once and goes on to the product or to drain. Replacement: we supply the Temptek CG-2A, an air-cooled portable chiller rated 2 tons at 50°F, against the 1.92 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin. The Temptek unit is a recirculating chiller with its own pump, so a one-pass installation needs a return line or a buffer tank; we work that out with the piping before quoting.
Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.