1-805-484-2992

Quotes - Sizing - Sales

PC-300G-36

Filtrine
Product Type Capacity Refrigerant
One-Pass Chiller Air-Cooled 2.08 Tons @ 50°F HFC

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PC-300G-36 as shown on this page.

Replacement chiller for the Filtrine PC-300G-36

Description

The Filtrine PC-300G-36 is a 2.08-ton one-pass air-cooled chiller from the PC line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 25,000 Btu/h, 2.08 tons, at 50°F outlet and 90°F ambient, 18,000 Btu/h at 30°F and 36,000 Btu/h at 68°F, the point its model number is named for. As a one-pass chiller it has no pump: the liquid enters under its own pressure, passes through the tank once and goes on to the product or to drain. Replacement: we supply the Temptek CG-3A, an air-cooled portable chiller rated 2.9 tons at 50°F, against the 2.08 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin. The Temptek unit is a recirculating chiller with its own pump, so a one-pass installation needs a return line or a buffer tank; we work that out with the piping before quoting.

Product Overview

Part Number:
PC-300G-36
Manufacturer:
Filtrine
Replacement Unit:
Temptek CG-3A

Published Capacity

Cooling Capacity at 50°F:
25,000 Btu/h (2.08 tons)
Cooling Capacity at 30°F:
18,000 Btu/h
Cooling Capacity at 68°F:
36,000 Btu/h
Rating Point:
90°F ambient, air-cooled (-A) model
Thermostat Range:
40 to 90°F standard

Configuration & Specifications

Style:
One-pass
Compressor:
Scroll, 3 hp
Condenser:
Fan-cooled (-A); water-cooled (-W) offered
Evaporator:
Immersion coil in a welded stainless tank
Refrigerant:
HFC (per the spec sheet)

Pump & Reservoir

  • Pump: Not fitted (one pass)
  • Cooling Tank: 30 gallons

Electrical

  • Supply Power: 208-230 V, 3 ph, 60 Hz or 460 V, 3 ph, 60 Hz
  • FLA Maximum: 16 or 8 A

Connections

Plumbing Connections In & Out:
3/4 in FPT

Dimensions & Weight

Cabinet (W x D x H):
62 x 32 x 48 in
Shipping Weight:
1,300 lbs

Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales