1-805-484-2992

Quotes - Sizing - Sales

PCP-150-15

Filtrine
Product Type Capacity Refrigerant
Recirculating Chiller Air-Cooled 0.75 Tons @ 50°F HFC

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PCP-150-15 as shown on this page.

Replacement chiller for the Filtrine PCP-150-15

Description

The Filtrine PCP-150-15 is a 0.75-ton closed-loop recirculating air-cooled chiller from the PCP line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 9,000 Btu/h, 0.75 tons, at 50°F outlet and 90°F ambient, 8,000 Btu/h at 30°F and 15,000 Btu/h at 68°F, the point its model number is named for. As a closed-loop chiller its sealed tank and pump recirculate a clean coolant at constant pressure and flow. Replacement: we supply the Temptek CF-.75A, a fractional-ton portable chiller rated 0.75 tons at 50°F, against the 0.75 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin.

Product Overview

Part Number:
PCP-150-15
Manufacturer:
Filtrine
Replacement Unit:
Temptek CF-.75A

Published Capacity

Cooling Capacity at 50°F:
9,000 Btu/h (0.75 tons)
Cooling Capacity at 30°F:
8,000 Btu/h
Cooling Capacity at 68°F:
15,000 Btu/h
Rating Point:
90°F ambient, air-cooled (-A) model
Thermostat Range:
40 to 90°F standard

Configuration & Specifications

Style:
Closed-loop recirculating
Compressor:
Welded hermetic, 1-1/2 hp
Condenser:
Fan-cooled (-A); water-cooled (-W) offered
Evaporator:
Immersion coil in a welded stainless tank
Refrigerant:
HFC (per the spec sheet)

Pump & Reservoir

  • Pump: 1/3 hp
  • Pump Capacity: 8 GPM @ 15 PSI
  • Cooling Tank: 16 gallons

Electrical

  • Supply Power: 208-230 V, 1 ph, 60 Hz

Connections

Plumbing Connections In & Out:
3/4 in FPT

Dimensions & Weight

Cabinet (W x D x H):
42 x 27 x 42 in
Shipping Weight:
600 lbs

Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales