Replacement unit for the Filtrine PCP Closed Loop Series

PCP Closed Loop Series

Filtrine's closed-loop chiller: a sealed stainless storage tank and a pump that recirculates clean coolant at constant pressure and flow.

PRODUCT TYPE CAPACITY MODELS
Recirculating Chiller Closed-Loop Recirculating 1,800 to 720,000 Btu/h 35

Specifications


Configuration & Size

Capacity:
1,800 to 720,000 Btu/h at 50°F
Models:
35 part numbers
Compressor:
1/4 to 2 x 40 hp
Pump:
1/14 to 5 hp
Tank:
2 to 510 gallons

Construction

  • Hermetic, scroll or semi-hermetic
  • Welded stainless cooling tank
  • Immersion coil evaporator
  • Bronze centrifugal pump, bypass
  • Enameled aluminum cabinet

Ratings

  • Rated at 30, 50 and 68°F outlet
  • 90°F ambient, air-cooled
  • Thermostat 40 to 90°F
  • HFC or HFO refrigerant

Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.

PCP Closed Loop Chillers, 35 Sizes

A Sealed Tank and a Steady Flow

Thirty-five sizes in one chart. From the PCP-25-2 at 1,800 Btu/h at 50°F outlet to the PCP-8000-860 at 720,000 Btu/h, all at 90°F ambient, with 1/4 hp to twin 40 hp compressors.

The tank is sealed. Filtrine's sheets describe a welded stainless storage tank with an immersion coil, a level gauge, fill port and clean-out, sealed to keep the coolant from evaporating or fouling.

The pump runs at constant pressure. From a 1/14 hp pump on the smallest sizes to 5 hp on the largest, with a manual bypass valve to set the flow on the mid and large units.

The compressor runs only as needed. Filtrine's storage design cycles the compressor rather than running it constantly, and holds the set point within about ±1.5°F on the small units.



a high-flow water discharge into an open basin

Compressor, sealed stainless tank with an immersion coil, and a recirculating pump in one cabinet.

Request a Quote

PCP Closed Loop Series Applications

Lasers and optics
Lasers and optics
Medical imaging
Medical imaging
Machine tools
Machine tools
Lab instruments
Lab instruments

schematic of the PCP Closed Loop series circuit, showing where the process fluid and the condenser heat go

Read the 50 Degree Column

A Filtrine model number is named for its 68°F capacity. The PCP-75-7 makes 7,600 Btu/h at 68°F outlet, 6,000 at 50°F and 4,500 at 30°F, so a unit chosen by its name for a 50°F loop is about a fifth smaller than it sounds. Size from the column you will actually run.

The leaving fluid temperature guide explains why capacity falls with set point.

Every part-number page below names the Temptek unit we supply in its place, sized to cover the 50°F figure: a Temptek CF to 1.5 tons, a CG air-cooled portable to 25 tons, a TTI central chiller above, and an MA module where Filtrine's size is remote-condenser only.
Call and talk it through with an engineer: 1-805-484-2992

Filtrine PCP Model Numbers and the 50°F Column

About 30 percent: Filtrine lists the PCP-1000S-140 at 140,000 Btu/h at 68°F outlet and 98,000 Btu/h at 50°F, about 8.2 tons. The PCP-75-7 drops only about 21 percent between the same columns, so the gap is not a fixed fraction; read each row. Going by the 140 in the name would overstate the unit by about three and a half tons.

Because its pump carries much less flow per ton: 80 GPM at 45 PSI against 720,000 Btu/h at 50°F outlet gives a rise of about 18°F, 720,000 divided by 500 x 80. That is a wide rise for a process chiller, and it only suits a loop designed for it. The small end runs the other way. The PCP-100-10, named for 10,000 Btu/h at 68°F, has a pump listed at 8 GPM at 15 PSI, a rise of about 2.5°F at that figure, the narrow rise laser and imaging loads are usually built around. Send the flow and the rise your equipment was designed for, since the Temptek pump selection follows the process, not the old pump label.

On the 50°F figure, exactly: the PCP-8000-860 is listed at 720,000 Btu/h at 50°F, which is 60 tons, and the Temptek MA-60-RC-C is a 60-ton module. The only margin comes from the rating condition, since Filtrine rates at 90°F ambient and Temptek at 95°F, the harder of the two. The MA is a module with a remote condenser, chosen because Filtrine builds that size with a remote condenser only, so the condenser location and the refrigerant line run are part of the job. If the loop runs colder than 50°F, or the old unit ran near its limit, ask us to look at the next step up.

Whether the equipment really needs that band or a tighter one, and how quickly its load changes. Filtrine's ±1.5°F applies to the small units, where the compressor cycles against the stored volume; a laser that steps from idle to full power in a second sees that swing differently from a machine tool that warms over an hour. State the tolerence at the instrument inlet, not at the chiller, since hose length and room temperature add to it. Also say whether the loop is sealed: the PCP tank is sealed against evaporation and fouling, and an imaging system that has run on clean coolant for years should stay that way.