1-805-484-2992

Quotes - Sizing - Sales

PCP-6000-660

Filtrine
Product Type Capacity Refrigerant
Recirculating Chiller Remote Condenser 45 Tons @ 50°F HFO

Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n PCP-6000-660 as shown on this page.

Replacement chiller for the Filtrine PCP-6000-660

Description

The Filtrine PCP-6000-660 is a 45-ton closed-loop recirculating air-cooled chiller from the PCP line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 540,000 Btu/h, 45 tons, at 50°F outlet and 90°F ambient, 380,000 Btu/h at 30°F and 660,000 Btu/h at 68°F, the point its model number is named for. As a closed-loop chiller its sealed tank and pump recirculate a clean coolant at constant pressure and flow. Filtrine offers this size with a remote air- or water-cooled condenser only. Replacement: we supply the Temptek MA-50-RC-C, an air-cooled chilling module with a remote condenser rated 46.4 tons at 50°F, against the 45 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin.

Product Overview

Part Number:
PCP-6000-660
Manufacturer:
Filtrine
Replacement Unit:
Temptek MA-50-RC-C

Published Capacity

Cooling Capacity at 50°F:
540,000 Btu/h (45 tons)
Cooling Capacity at 30°F:
380,000 Btu/h
Cooling Capacity at 68°F:
660,000 Btu/h
Rating Point:
90°F ambient, air-cooled (-A) model
Thermostat Range:
40 to 90°F standard

Configuration & Specifications

Style:
Closed-loop recirculating
Compressor:
Semi-hermetic, 2 x 30 hp
Condenser:
Remote air- or water-cooled only
Evaporator:
Immersion coil in a welded stainless tank
Refrigerant:
HFO (per the spec sheet)

Pump & Reservoir

  • Pump: 5 hp
  • Pump Capacity: 80 GPM @ 45 PSI
  • Cooling Tank: 340 gallons

Electrical

  • Supply Power: 230 V, 3 ph, 60 Hz or 460 V, 3 ph, 60 Hz
  • FLA Maximum: 250 or 126 A

Connections

Plumbing Connections In & Out:
2-1/2 in MPT

Dimensions & Weight

Cabinet (W x D x H):
126 x 62 x 80 in
Shipping Weight:
8,500 lbs

Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.

Quote Request Form:

Questions?

1-805-484-2992

Quotes - Sizing - Sales