| Product | Type | Capacity | Refrigerant |
|---|---|---|---|
| Recirculating Chiller | Air-Cooled | 1.92 Tons @ 50°F | HFO |
Note: Unit pictured is the replacement unit, representative of standard unit, and may not exactly depict p/n POC-200-30 as shown on this page.
The Filtrine POC-200-30 is a 1.92-ton open-loop recirculating air-cooled chiller from the POC line, built around Filtrine's storage-type stainless cooling tank with an immersion coil evaporator. Filtrine's chart lists 23,000 Btu/h, 1.92 tons, at 50°F outlet and 90°F ambient, 13,500 Btu/h at 30°F and 30,000 Btu/h at 68°F, the point its model number is named for. As an open-loop chiller its pump draws from an open tank or sump and returns to it, with the thermostat sensing the make-up liquid. Replacement: we supply the Temptek CG-2A, an air-cooled portable chiller rated 2 tons at 50°F, against the 1.92 tons Filtrine publishes for this unit at 50°F outlet and 90°F ambient. Filtrine rates at 90°F ambient and Temptek at 95°F, the harder condition, so a Temptek unit that covers the Filtrine figure keeps a margin. The Temptek unit runs a closed loop from its own tank, so an open sump on the old system is piped as the return or replaced.
Specifications sourced from Filtrine's published Process Chillers Specifications chart and per-model spec sheets (filtrine.com), October 2026. Filtrine is a trademark of its owner; referenced here for cross-reference only. Filtrine notes that dimensions and shipping weights vary with options. Confirm against the unit nameplate before ordering.